Kabelarea för 110 Ampere vid 35 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 35 m vid 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 4.08V (1.02%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 4.71V (1.18%)
Voltage at Load395.9 VLine Loss: 776.8 W
Max Power & Breaker76.21 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A95.14 V (23.78%)304.9 V156.93 V (39.23%)18125.8 WDrop High
2.5 mm²24 A18 A57.08 V (14.27%)342.9 V94.16 V (23.54%)10875.5 WDrop High
4 mm²32 A25 A35.68 V (8.92%)364.3 V58.85 V (14.71%)6797.2 WDrop High
6 mm²41 A32 A23.78 V (5.95%)376.2 V39.23 V (9.81%)4531.4 WDrop High
10 mm²57 A44 A14.27 V (3.57%)385.7 V23.54 V (5.88%)2718.9 WDrop High
16 mm²76 A59 A8.92 V (2.23%)391.1 V14.71 V (3.68%)1699.3 WDrop High
25 mm²101 A78 A5.71 V (1.43%)394.3 V9.42 V (2.35%)1087.5 WDrop High
35 mm²125 A97 A4.08 V (1.02%)395.9 V6.73 V (1.68%)776.8 W✓ OK (≤3%)
50 mm²151 A118 A2.85 V (0.71%)397.1 V4.71 V (1.18%)543.8 W✓ OK (≤3%)
70 mm²192 A150 A2.04 V (0.51%)398.0 V3.36 V (0.84%)388.4 W✓ OK (≤3%)
95 mm²232 A181 A1.5 V (0.38%)398.5 V2.48 V (0.62%)286.2 W✓ OK (≤3%)
120 mm²269 A210 A1.19 V (0.3%)398.8 V1.96 V (0.49%)226.6 W✓ OK (≤3%)
150 mm²309 A241 A0.95 V (0.24%)399.0 V1.57 V (0.39%)181.3 W✓ OK (≤3%)
185 mm²353 A275 A0.77 V (0.19%)399.2 V1.27 V (0.32%)147.0 W✓ OK (≤3%)
240 mm²415 A324 A0.59 V (0.15%)399.4 V0.98 V (0.25%)113.3 W✓ OK (≤3%)
300 mm²477 A372 A0.48 V (0.12%)399.5 V0.78 V (0.2%)90.6 W✓ OK (≤3%)
400 mm²570 A445 A0.36 V (0.09%)399.6 V0.59 V (0.15%)68.0 W✓ OK (≤3%)

FAQ — Kabelarea för 110 Ampere vid 35 Meter (400V)

Vilken kabelarea krävs för 110A vid 35 meter (400V)?

För 110 Ampere över 35 meter vid 400V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (4.08V / 1.02%).

Hur stor effekt motsvarar 110A vid 400V?

Det motsvarar 76.21 kW med en rekommenderad säkring på 110A.