Kabelarea för 125 Ampere vid 250 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 125 A över 250 m vid 230V.

Copper Cable (≤3% Drop)240 mm²Drop: 5.57V (2.42%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.52V (2.4%)
Voltage at Load224.4 VLine Loss: 696.6 W
Max Power & Breaker28.75 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A891.67 V (387.68%)0.0 V1470.83 V (639.49%)111458.3 WDrop High
2.5 mm²24 A18 A535.0 V (232.61%)0.0 V882.5 V (383.7%)66875.0 WDrop High
4 mm²32 A25 A334.38 V (145.38%)0.0 V551.56 V (239.81%)41796.9 WDrop High
6 mm²41 A32 A222.92 V (96.92%)7.1 V367.71 V (159.87%)27864.6 WDrop High
10 mm²57 A44 A133.75 V (58.15%)96.3 V220.62 V (95.92%)16718.7 WDrop High
16 mm²76 A59 A83.59 V (36.35%)146.4 V137.89 V (59.95%)10449.2 WDrop High
25 mm²101 A78 A53.5 V (23.26%)176.5 V88.25 V (38.37%)6687.5 WDrop High
35 mm²125 A97 A38.21 V (16.61%)191.8 V63.04 V (27.41%)4776.8 WDrop High
50 mm²151 A118 A26.75 V (11.63%)203.2 V44.12 V (19.18%)3343.8 WDrop High
70 mm²192 A150 A19.11 V (8.31%)210.9 V31.52 V (13.7%)2388.4 WDrop High
95 mm²232 A181 A14.08 V (6.12%)215.9 V23.22 V (10.1%)1759.9 WDrop High
120 mm²269 A210 A11.15 V (4.85%)218.9 V18.39 V (7.99%)1393.2 W~ ≤5%
150 mm²309 A241 A8.92 V (3.88%)221.1 V14.71 V (6.39%)1114.6 W~ ≤5%
185 mm²353 A275 A7.23 V (3.14%)222.8 V11.93 V (5.19%)903.7 W~ ≤5%
240 mm²415 A324 A5.57 V (2.42%)224.4 V9.19 V (4.0%)696.6 W✓ OK (≤3%)
300 mm²477 A372 A4.46 V (1.94%)225.5 V7.35 V (3.2%)557.3 W✓ OK (≤3%)
400 mm²570 A445 A3.34 V (1.45%)226.7 V5.52 V (2.4%)418.0 W✓ OK (≤3%)

FAQ — Kabelarea för 125 Ampere vid 250 Meter (230V)

Vilken kabelarea krävs för 125A vid 250 meter (230V)?

För 125 Ampere över 250 meter vid 230V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (5.57V / 2.42%).

Hur stor effekt motsvarar 125A vid 230V?

Det motsvarar 28.75 kW med en rekommenderad säkring på 125A.