Kabelarea för 63 Ampere vid 250 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 250 m vid 230V.

Copper Cable (≤3% Drop)120 mm²Drop: 5.62V (2.44%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 6.01V (2.61%)
Voltage at Load224.4 VLine Loss: 353.9 W
Max Power & Breaker14.49 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A449.4 V (195.39%)0.0 V741.3 V (322.3%)28312.2 WDrop High
2.5 mm²24 A18 A269.64 V (117.23%)0.0 V444.78 V (193.38%)16987.3 WDrop High
4 mm²32 A25 A168.52 V (73.27%)61.5 V277.99 V (120.86%)10617.1 WDrop High
6 mm²41 A32 A112.35 V (48.85%)117.7 V185.32 V (80.58%)7078.0 WDrop High
10 mm²57 A44 A67.41 V (29.31%)162.6 V111.19 V (48.35%)4246.8 WDrop High
16 mm²76 A59 A42.13 V (18.32%)187.9 V69.5 V (30.22%)2654.3 WDrop High
25 mm²101 A78 A26.96 V (11.72%)203.0 V44.48 V (19.34%)1698.7 WDrop High
35 mm²125 A97 A19.26 V (8.37%)210.7 V31.77 V (13.81%)1213.4 WDrop High
50 mm²151 A118 A13.48 V (5.86%)216.5 V22.24 V (9.67%)849.4 WDrop High
70 mm²192 A150 A9.63 V (4.19%)220.4 V15.88 V (6.91%)606.7 W~ ≤5%
95 mm²232 A181 A7.1 V (3.09%)222.9 V11.7 V (5.09%)447.0 W~ ≤5%
120 mm²269 A210 A5.62 V (2.44%)224.4 V9.27 V (4.03%)353.9 W✓ OK (≤3%)
150 mm²309 A241 A4.49 V (1.95%)225.5 V7.41 V (3.22%)283.1 W✓ OK (≤3%)
185 mm²353 A275 A3.64 V (1.58%)226.4 V6.01 V (2.61%)229.6 W✓ OK (≤3%)
240 mm²415 A324 A2.81 V (1.22%)227.2 V4.63 V (2.01%)177.0 W✓ OK (≤3%)
300 mm²477 A372 A2.25 V (0.98%)227.8 V3.71 V (1.61%)141.6 W✓ OK (≤3%)
400 mm²570 A445 A1.69 V (0.73%)228.3 V2.78 V (1.21%)106.2 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 250 Meter (230V)

Vilken kabelarea krävs för 63A vid 250 meter (230V)?

För 63 Ampere över 250 meter vid 230V rekommenderas 120 mm² kopparkabel för att hålla spänningsfallet under 3% (5.62V / 2.44%).

Hur stor effekt motsvarar 63A vid 230V?

Det motsvarar 14.49 kW med en rekommenderad säkring på 63A.