Kabelarea för 160 Ampere vid 250 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 160 A över 250 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 5.71V (2.48%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.06V (3.07%)
Voltage at Load224.3 VLine Loss: 913.1 W
Max Power & Breaker36.8 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1141.33 V (496.23%)0.0 V1882.67 V (818.55%)182613.3 WDrop High
2.5 mm²24 A18 A684.8 V (297.74%)0.0 V1129.6 V (491.13%)109568.0 WDrop High
4 mm²32 A25 A428.0 V (186.09%)0.0 V706.0 V (306.96%)68480.0 WDrop High
6 mm²41 A32 A285.33 V (124.06%)0.0 V470.67 V (204.64%)45653.3 WDrop High
10 mm²57 A44 A171.2 V (74.43%)58.8 V282.4 V (122.78%)27392.0 WDrop High
16 mm²76 A59 A107.0 V (46.52%)123.0 V176.5 V (76.74%)17120.0 WDrop High
25 mm²101 A78 A68.48 V (29.77%)161.5 V112.96 V (49.11%)10956.8 WDrop High
35 mm²125 A97 A48.91 V (21.27%)181.1 V80.69 V (35.08%)7826.3 WDrop High
50 mm²151 A118 A34.24 V (14.89%)195.8 V56.48 V (24.56%)5478.4 WDrop High
70 mm²192 A150 A24.46 V (10.63%)205.5 V40.34 V (17.54%)3913.1 WDrop High
95 mm²232 A181 A18.02 V (7.84%)212.0 V29.73 V (12.92%)2883.4 WDrop High
120 mm²269 A210 A14.27 V (6.2%)215.7 V23.53 V (10.23%)2282.7 WDrop High
150 mm²309 A241 A11.41 V (4.96%)218.6 V18.83 V (8.19%)1826.1 W~ ≤5%
185 mm²353 A275 A9.25 V (4.02%)220.7 V15.26 V (6.64%)1480.6 W~ ≤5%
240 mm²415 A324 A7.13 V (3.1%)222.9 V11.77 V (5.12%)1141.3 W~ ≤5%
300 mm²477 A372 A5.71 V (2.48%)224.3 V9.41 V (4.09%)913.1 W✓ OK (≤3%)
400 mm²570 A445 A4.28 V (1.86%)225.7 V7.06 V (3.07%)684.8 W✓ OK (≤3%)

FAQ — Kabelarea för 160 Ampere vid 250 Meter (230V)

Vilken kabelarea krävs för 160A vid 250 meter (230V)?

För 160 Ampere över 250 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (5.71V / 2.48%).

Hur stor effekt motsvarar 160A vid 230V?

Det motsvarar 36.8 kW med en rekommenderad säkring på 160A.