Kabelarea för 125 Ampere vid 5 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 125 A över 5 m vid 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 0.76V (0.33%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 0.63V (0.27%)
Voltage at Load229.2 VLine Loss: 95.5 W
Max Power & Breaker28.75 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A17.83 V (7.75%)212.2 V29.42 V (12.79%)2229.2 WDrop High
2.5 mm²24 A18 A10.7 V (4.65%)219.3 V17.65 V (7.67%)1337.5 WDrop High
4 mm²32 A25 A6.69 V (2.91%)223.3 V11.03 V (4.8%)835.9 WDrop High
6 mm²41 A32 A4.46 V (1.94%)225.5 V7.35 V (3.2%)557.3 WDrop High
10 mm²57 A44 A2.67 V (1.16%)227.3 V4.41 V (1.92%)334.4 WDrop High
16 mm²76 A59 A1.67 V (0.73%)228.3 V2.76 V (1.2%)209.0 WDrop High
25 mm²101 A78 A1.07 V (0.47%)228.9 V1.76 V (0.77%)133.8 WDrop High
35 mm²125 A97 A0.76 V (0.33%)229.2 V1.26 V (0.55%)95.5 W✓ OK (≤3%)
50 mm²151 A118 A0.54 V (0.23%)229.5 V0.88 V (0.38%)66.9 W✓ OK (≤3%)
70 mm²192 A150 A0.38 V (0.17%)229.6 V0.63 V (0.27%)47.8 W✓ OK (≤3%)
95 mm²232 A181 A0.28 V (0.12%)229.7 V0.46 V (0.2%)35.2 W✓ OK (≤3%)
120 mm²269 A210 A0.22 V (0.1%)229.8 V0.37 V (0.16%)27.9 W✓ OK (≤3%)
150 mm²309 A241 A0.18 V (0.08%)229.8 V0.29 V (0.13%)22.3 W✓ OK (≤3%)
185 mm²353 A275 A0.14 V (0.06%)229.9 V0.24 V (0.1%)18.1 W✓ OK (≤3%)
240 mm²415 A324 A0.11 V (0.05%)229.9 V0.18 V (0.08%)13.9 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.04%)229.9 V0.15 V (0.06%)11.1 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.03%)229.9 V0.11 V (0.05%)8.4 W✓ OK (≤3%)

FAQ — Kabelarea för 125 Ampere vid 5 Meter (230V)

Vilken kabelarea krävs för 125A vid 5 meter (230V)?

För 125 Ampere över 5 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (0.76V / 0.33%).

Hur stor effekt motsvarar 125A vid 230V?

Det motsvarar 28.75 kW med en rekommenderad säkring på 125A.