Kabelarea för 63 Ampere vid 35 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 35 m vid 400V.
Copper Cable (≤3% Drop)16 mm²Drop: 5.11V (1.28%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 5.39V (1.35%)
Voltage at Load394.9 VLine Loss: 557.4 W
Max Power & Breaker43.65 kW63A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 54.49 V (13.62%) | 345.5 V | 89.88 V (22.47%) | 5945.6 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 32.69 V (8.17%) | 367.3 V | 53.93 V (13.48%) | 3567.3 W | Drop High |
| 4 mm² | 32 A | 25 A | 20.43 V (5.11%) | 379.6 V | 33.7 V (8.43%) | 2229.6 W | Drop High |
| 6 mm² | 41 A | 32 A | 13.62 V (3.41%) | 386.4 V | 22.47 V (5.62%) | 1486.4 W | Drop High |
| 10 mm² | 57 A | 44 A | 8.17 V (2.04%) | 391.8 V | 13.48 V (3.37%) | 891.8 W | Drop High |
| 16 mm² | 76 A | 59 A | 5.11 V (1.28%) | 394.9 V | 8.43 V (2.11%) | 557.4 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 3.27 V (0.82%) | 396.7 V | 5.39 V (1.35%) | 356.7 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 2.34 V (0.58%) | 397.7 V | 3.85 V (0.96%) | 254.8 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 1.63 V (0.41%) | 398.4 V | 2.7 V (0.67%) | 178.4 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 1.17 V (0.29%) | 398.8 V | 1.93 V (0.48%) | 127.4 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.86 V (0.22%) | 399.1 V | 1.42 V (0.35%) | 93.9 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.68 V (0.17%) | 399.3 V | 1.12 V (0.28%) | 74.3 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.54 V (0.14%) | 399.5 V | 0.9 V (0.22%) | 59.5 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.44 V (0.11%) | 399.6 V | 0.73 V (0.18%) | 48.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.34 V (0.09%) | 399.7 V | 0.56 V (0.14%) | 37.2 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.27 V (0.07%) | 399.7 V | 0.45 V (0.11%) | 29.7 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.2 V (0.05%) | 399.8 V | 0.34 V (0.08%) | 22.3 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 63 Ampere vid 35 Meter (400V)
Vilken kabelarea krävs för 63A vid 35 meter (400V)?
För 63 Ampere över 35 meter vid 400V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (5.11V / 1.28%).
Hur stor effekt motsvarar 63A vid 400V?
Det motsvarar 43.65 kW med en rekommenderad säkring på 63A.
Related Lengths & Currents (400V)
63A · 5m (400V)63A · 10m (400V)63A · 15m (400V)63A · 20m (400V)63A · 25m (400V)63A · 30m (400V)63A · 40m (400V)63A · 45m (400V)63A · 50m (400V)63A · 60m (400V)63A · 70m (400V)10A · 35m (400V)16A · 35m (400V)20A · 35m (400V)25A · 35m (400V)32A · 35m (400V)40A · 35m (400V)50A · 35m (400V)80A · 35m (400V)100A · 35m (400V)125A · 35m (400V)160A · 35m (400V)200A · 35m (400V)