Kabelarea för 160 Ampere vid 35 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 160 A över 35 m vid 400V.
Copper Cable (≤3% Drop)70 mm²Drop: 2.97V (0.74%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 3.6V (0.9%)
Voltage at Load397.0 VLine Loss: 821.8 W
Max Power & Breaker110.85 kW160A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 138.38 V (34.59%) | 261.6 V | 228.26 V (57.07%) | 38348.8 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 83.03 V (20.76%) | 317.0 V | 136.96 V (34.24%) | 23009.3 W | Drop High |
| 4 mm² | 32 A | 25 A | 51.89 V (12.97%) | 348.1 V | 85.6 V (21.4%) | 14380.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 34.59 V (8.65%) | 365.4 V | 57.07 V (14.27%) | 9587.2 W | Drop High |
| 10 mm² | 57 A | 44 A | 20.76 V (5.19%) | 379.2 V | 34.24 V (8.56%) | 5752.3 W | Drop High |
| 16 mm² | 76 A | 59 A | 12.97 V (3.24%) | 387.0 V | 21.4 V (5.35%) | 3595.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 8.3 V (2.08%) | 391.7 V | 13.7 V (3.42%) | 2300.9 W | Drop High |
| 35 mm² | 125 A | 97 A | 5.93 V (1.48%) | 394.1 V | 9.78 V (2.45%) | 1643.5 W | Drop High |
| 50 mm² | 151 A | 118 A | 4.15 V (1.04%) | 395.8 V | 6.85 V (1.71%) | 1150.5 W | Drop High |
| 70 mm² | 192 A | 150 A | 2.97 V (0.74%) | 397.0 V | 4.89 V (1.22%) | 821.8 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 2.18 V (0.55%) | 397.8 V | 3.6 V (0.9%) | 605.5 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.73 V (0.43%) | 398.3 V | 2.85 V (0.71%) | 479.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.38 V (0.35%) | 398.6 V | 2.28 V (0.57%) | 383.5 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 1.12 V (0.28%) | 398.9 V | 1.85 V (0.46%) | 310.9 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.86 V (0.22%) | 399.1 V | 1.43 V (0.36%) | 239.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.69 V (0.17%) | 399.3 V | 1.14 V (0.29%) | 191.7 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.52 V (0.13%) | 399.5 V | 0.86 V (0.21%) | 143.8 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 160 Ampere vid 35 Meter (400V)
Vilken kabelarea krävs för 160A vid 35 meter (400V)?
För 160 Ampere över 35 meter vid 400V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (2.97V / 0.74%).
Hur stor effekt motsvarar 160A vid 400V?
Det motsvarar 110.85 kW med en rekommenderad säkring på 160A.
Related Lengths & Currents (400V)
160A · 5m (400V)160A · 10m (400V)160A · 15m (400V)160A · 20m (400V)160A · 25m (400V)160A · 30m (400V)160A · 40m (400V)160A · 45m (400V)160A · 50m (400V)160A · 60m (400V)160A · 70m (400V)10A · 35m (400V)16A · 35m (400V)20A · 35m (400V)25A · 35m (400V)32A · 35m (400V)40A · 35m (400V)50A · 35m (400V)63A · 35m (400V)80A · 35m (400V)100A · 35m (400V)125A · 35m (400V)200A · 35m (400V)