Kabelarea för 150 Ampere vid 80 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 150 A över 80 m vid 230V.

Copper Cable (≤3% Drop)95 mm²Drop: 5.41V (2.35%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 5.65V (2.46%)
Voltage at Load224.6 VLine Loss: 810.9 W
Max Power & Breaker34.5 kW150A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A342.4 V (148.87%)0.0 V564.8 V (245.57%)51360.0 WDrop High
2.5 mm²24 A18 A205.44 V (89.32%)24.6 V338.88 V (147.34%)30816.0 WDrop High
4 mm²32 A25 A128.4 V (55.83%)101.6 V211.8 V (92.09%)19260.0 WDrop High
6 mm²41 A32 A85.6 V (37.22%)144.4 V141.2 V (61.39%)12840.0 WDrop High
10 mm²57 A44 A51.36 V (22.33%)178.6 V84.72 V (36.83%)7704.0 WDrop High
16 mm²76 A59 A32.1 V (13.96%)197.9 V52.95 V (23.02%)4815.0 WDrop High
25 mm²101 A78 A20.54 V (8.93%)209.5 V33.89 V (14.73%)3081.6 WDrop High
35 mm²125 A97 A14.67 V (6.38%)215.3 V24.21 V (10.52%)2201.1 WDrop High
50 mm²151 A118 A10.27 V (4.47%)219.7 V16.94 V (7.37%)1540.8 W~ ≤5%
70 mm²192 A150 A7.34 V (3.19%)222.7 V12.1 V (5.26%)1100.6 W~ ≤5%
95 mm²232 A181 A5.41 V (2.35%)224.6 V8.92 V (3.88%)810.9 W✓ OK (≤3%)
120 mm²269 A210 A4.28 V (1.86%)225.7 V7.06 V (3.07%)642.0 W✓ OK (≤3%)
150 mm²309 A241 A3.42 V (1.49%)226.6 V5.65 V (2.46%)513.6 W✓ OK (≤3%)
185 mm²353 A275 A2.78 V (1.21%)227.2 V4.58 V (1.99%)416.4 W✓ OK (≤3%)
240 mm²415 A324 A2.14 V (0.93%)227.9 V3.53 V (1.53%)321.0 W✓ OK (≤3%)
300 mm²477 A372 A1.71 V (0.74%)228.3 V2.82 V (1.23%)256.8 W✓ OK (≤3%)
400 mm²570 A445 A1.28 V (0.56%)228.7 V2.12 V (0.92%)192.6 W✓ OK (≤3%)

FAQ — Kabelarea för 150 Ampere vid 80 Meter (230V)

Vilken kabelarea krävs för 150A vid 80 meter (230V)?

För 150 Ampere över 80 meter vid 230V rekommenderas 95 mm² kopparkabel för att hålla spänningsfallet under 3% (5.41V / 2.35%).

Hur stor effekt motsvarar 150A vid 230V?

Det motsvarar 34.5 kW med en rekommenderad säkring på 150A.