Kabelarea för 16 Ampere vid 5 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 16 A över 5 m vid 230V.

Copper Cable (≤3% Drop)1.5 mm²Drop: 2.28V (0.99%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 2.26V (0.98%)
Voltage at Load227.7 VLine Loss: 36.5 W
Max Power & Breaker3.68 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2.28 V (0.99%)227.7 V3.77 V (1.64%)36.5 W✓ OK (≤3%)
2.5 mm²24 A18 A1.37 V (0.6%)228.6 V2.26 V (0.98%)21.9 W✓ OK (≤3%)
4 mm²32 A25 A0.86 V (0.37%)229.1 V1.41 V (0.61%)13.7 W✓ OK (≤3%)
6 mm²41 A32 A0.57 V (0.25%)229.4 V0.94 V (0.41%)9.1 W✓ OK (≤3%)
10 mm²57 A44 A0.34 V (0.15%)229.7 V0.56 V (0.25%)5.5 W✓ OK (≤3%)
16 mm²76 A59 A0.21 V (0.09%)229.8 V0.35 V (0.15%)3.4 W✓ OK (≤3%)
25 mm²101 A78 A0.14 V (0.06%)229.9 V0.23 V (0.1%)2.2 W✓ OK (≤3%)
35 mm²125 A97 A0.1 V (0.04%)229.9 V0.16 V (0.07%)1.6 W✓ OK (≤3%)
50 mm²151 A118 A0.07 V (0.03%)229.9 V0.11 V (0.05%)1.1 W✓ OK (≤3%)
70 mm²192 A150 A0.05 V (0.02%)230.0 V0.08 V (0.04%)0.8 W✓ OK (≤3%)
95 mm²232 A181 A0.04 V (0.02%)230.0 V0.06 V (0.03%)0.6 W✓ OK (≤3%)
120 mm²269 A210 A0.03 V (0.01%)230.0 V0.05 V (0.02%)0.5 W✓ OK (≤3%)
150 mm²309 A241 A0.02 V (0.01%)230.0 V0.04 V (0.02%)0.4 W✓ OK (≤3%)
185 mm²353 A275 A0.02 V (0.01%)230.0 V0.03 V (0.01%)0.3 W✓ OK (≤3%)
240 mm²415 A324 A0.01 V (0.01%)230.0 V0.02 V (0.01%)0.2 W✓ OK (≤3%)
300 mm²477 A372 A0.01 V (0.0%)230.0 V0.02 V (0.01%)0.2 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.0%)230.0 V0.01 V (0.01%)0.1 W✓ OK (≤3%)

FAQ — Kabelarea för 16 Ampere vid 5 Meter (230V)

Vilken kabelarea krävs för 16A vid 5 meter (230V)?

För 16 Ampere över 5 meter vid 230V rekommenderas 1.5 mm² kopparkabel för att hålla spänningsfallet under 3% (2.28V / 0.99%).

Hur stor effekt motsvarar 16A vid 230V?

Det motsvarar 3.68 kW med en rekommenderad säkring på 16A.