⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 16 Ampere vid 15 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 16 A över 15 m vid 230V.

Copper Cable (≤3% Drop)1.5 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 6.78V (2.95%)
Voltage at Load223.2 VLine Loss: 109.6 W
Max Power & Breaker3.68 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6.85 V (2.98%)223.2 V11.3 V (4.91%)109.6 W✓ OK (≤3%)
2.5 mm²24 A18 A4.11 V (1.79%)225.9 V6.78 V (2.95%)65.7 W✓ OK (≤3%)
4 mm²32 A25 A2.57 V (1.12%)227.4 V4.24 V (1.84%)41.1 W✓ OK (≤3%)
6 mm²41 A32 A1.71 V (0.74%)228.3 V2.82 V (1.23%)27.4 W✓ OK (≤3%)
10 mm²57 A44 A1.03 V (0.45%)229.0 V1.69 V (0.74%)16.4 W✓ OK (≤3%)
16 mm²76 A59 A0.64 V (0.28%)229.4 V1.06 V (0.46%)10.3 W✓ OK (≤3%)
25 mm²101 A78 A0.41 V (0.18%)229.6 V0.68 V (0.29%)6.6 W✓ OK (≤3%)
35 mm²125 A97 A0.29 V (0.13%)229.7 V0.48 V (0.21%)4.7 W✓ OK (≤3%)
50 mm²151 A118 A0.21 V (0.09%)229.8 V0.34 V (0.15%)3.3 W✓ OK (≤3%)
70 mm²192 A150 A0.15 V (0.06%)229.9 V0.24 V (0.11%)2.3 W✓ OK (≤3%)
95 mm²232 A181 A0.11 V (0.05%)229.9 V0.18 V (0.08%)1.7 W✓ OK (≤3%)
120 mm²269 A210 A0.09 V (0.04%)229.9 V0.14 V (0.06%)1.4 W✓ OK (≤3%)
150 mm²309 A241 A0.07 V (0.03%)229.9 V0.11 V (0.05%)1.1 W✓ OK (≤3%)
185 mm²353 A275 A0.06 V (0.02%)229.9 V0.09 V (0.04%)0.9 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.02%)230.0 V0.07 V (0.03%)0.7 W✓ OK (≤3%)
300 mm²477 A372 A0.03 V (0.01%)230.0 V0.06 V (0.02%)0.5 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.01%)230.0 V0.04 V (0.02%)0.4 W✓ OK (≤3%)

FAQ — Kabelarea för 16 Ampere vid 15 Meter (230V)

Vilken kabelarea krävs för 16A vid 15 meter (230V)?

För 16 Ampere över 15 meter vid 230V rekommenderas 1.5 mm² kopparkabel för att hålla spänningsfallet under 3% (6.85V / 2.98%).

Hur stor effekt motsvarar 16A vid 230V?

Det motsvarar 3.68 kW med en rekommenderad säkring på 16A.