Kabelarea för 160 Ampere vid 10 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 160 A över 10 m vid 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 0.85V (0.21%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 1.03V (0.26%)
Voltage at Load399.2 VLine Loss: 234.8 W
Max Power & Breaker110.85 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A39.54 V (9.88%)360.5 V65.22 V (16.3%)10956.8 WDrop High
2.5 mm²24 A18 A23.72 V (5.93%)376.3 V39.13 V (9.78%)6574.1 WDrop High
4 mm²32 A25 A14.83 V (3.71%)385.2 V24.46 V (6.11%)4108.8 WDrop High
6 mm²41 A32 A9.88 V (2.47%)390.1 V16.3 V (4.08%)2739.2 WDrop High
10 mm²57 A44 A5.93 V (1.48%)394.1 V9.78 V (2.45%)1643.5 WDrop High
16 mm²76 A59 A3.71 V (0.93%)396.3 V6.11 V (1.53%)1027.2 WDrop High
25 mm²101 A78 A2.37 V (0.59%)397.6 V3.91 V (0.98%)657.4 WDrop High
35 mm²125 A97 A1.69 V (0.42%)398.3 V2.8 V (0.7%)469.6 WDrop High
50 mm²151 A118 A1.19 V (0.3%)398.8 V1.96 V (0.49%)328.7 WDrop High
70 mm²192 A150 A0.85 V (0.21%)399.2 V1.4 V (0.35%)234.8 W✓ OK (≤3%)
95 mm²232 A181 A0.62 V (0.16%)399.4 V1.03 V (0.26%)173.0 W✓ OK (≤3%)
120 mm²269 A210 A0.49 V (0.12%)399.5 V0.82 V (0.2%)137.0 W✓ OK (≤3%)
150 mm²309 A241 A0.4 V (0.1%)399.6 V0.65 V (0.16%)109.6 W✓ OK (≤3%)
185 mm²353 A275 A0.32 V (0.08%)399.7 V0.53 V (0.13%)88.8 W✓ OK (≤3%)
240 mm²415 A324 A0.25 V (0.06%)399.8 V0.41 V (0.1%)68.5 W✓ OK (≤3%)
300 mm²477 A372 A0.2 V (0.05%)399.8 V0.33 V (0.08%)54.8 W✓ OK (≤3%)
400 mm²570 A445 A0.15 V (0.04%)399.9 V0.24 V (0.06%)41.1 W✓ OK (≤3%)