Kabelarea för 175 Ampere vid 15 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 175 A över 15 m vid 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 1.6V (0.7%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 1.95V (0.85%)
Voltage at Load228.4 VLine Loss: 280.9 W
Max Power & Breaker40.25 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A74.9 V (32.57%)155.1 V123.55 V (53.72%)13107.5 WDrop High
2.5 mm²24 A18 A44.94 V (19.54%)185.1 V74.13 V (32.23%)7864.5 WDrop High
4 mm²32 A25 A28.09 V (12.21%)201.9 V46.33 V (20.14%)4915.3 WDrop High
6 mm²41 A32 A18.72 V (8.14%)211.3 V30.89 V (13.43%)3276.9 WDrop High
10 mm²57 A44 A11.24 V (4.88%)218.8 V18.53 V (8.06%)1966.1 WDrop High
16 mm²76 A59 A7.02 V (3.05%)223.0 V11.58 V (5.04%)1228.8 WDrop High
25 mm²101 A78 A4.49 V (1.95%)225.5 V7.41 V (3.22%)786.5 WDrop High
35 mm²125 A97 A3.21 V (1.4%)226.8 V5.29 V (2.3%)561.8 WDrop High
50 mm²151 A118 A2.25 V (0.98%)227.8 V3.71 V (1.61%)393.2 WDrop High
70 mm²192 A150 A1.6 V (0.7%)228.4 V2.65 V (1.15%)280.9 W✓ OK (≤3%)
95 mm²232 A181 A1.18 V (0.51%)228.8 V1.95 V (0.85%)207.0 W✓ OK (≤3%)
120 mm²269 A210 A0.94 V (0.41%)229.1 V1.54 V (0.67%)163.8 W✓ OK (≤3%)
150 mm²309 A241 A0.75 V (0.33%)229.3 V1.24 V (0.54%)131.1 W✓ OK (≤3%)
185 mm²353 A275 A0.61 V (0.26%)229.4 V1.0 V (0.44%)106.3 W✓ OK (≤3%)
240 mm²415 A324 A0.47 V (0.2%)229.5 V0.77 V (0.34%)81.9 W✓ OK (≤3%)
300 mm²477 A372 A0.37 V (0.16%)229.6 V0.62 V (0.27%)65.5 W✓ OK (≤3%)
400 mm²570 A445 A0.28 V (0.12%)229.7 V0.46 V (0.2%)49.2 W✓ OK (≤3%)

FAQ — Kabelarea för 175 Ampere vid 15 Meter (230V)

Vilken kabelarea krävs för 175A vid 15 meter (230V)?

För 175 Ampere över 15 meter vid 230V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (1.6V / 0.7%).

Hur stor effekt motsvarar 175A vid 230V?

Det motsvarar 40.25 kW med en rekommenderad säkring på 175A.