Kabelarea för 63 Ampere vid 15 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 15 m vid 230V.

Copper Cable (≤3% Drop)16 mm²Drop: 2.53V (1.1%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 2.67V (1.16%)
Voltage at Load227.5 VLine Loss: 159.3 W
Max Power & Breaker14.49 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A26.96 V (11.72%)203.0 V44.48 V (19.34%)1698.7 WDrop High
2.5 mm²24 A18 A16.18 V (7.03%)213.8 V26.69 V (11.6%)1019.2 WDrop High
4 mm²32 A25 A10.11 V (4.4%)219.9 V16.68 V (7.25%)637.0 WDrop High
6 mm²41 A32 A6.74 V (2.93%)223.3 V11.12 V (4.83%)424.7 WDrop High
10 mm²57 A44 A4.04 V (1.76%)226.0 V6.67 V (2.9%)254.8 WDrop High
16 mm²76 A59 A2.53 V (1.1%)227.5 V4.17 V (1.81%)159.3 W✓ OK (≤3%)
25 mm²101 A78 A1.62 V (0.7%)228.4 V2.67 V (1.16%)101.9 W✓ OK (≤3%)
35 mm²125 A97 A1.16 V (0.5%)228.8 V1.91 V (0.83%)72.8 W✓ OK (≤3%)
50 mm²151 A118 A0.81 V (0.35%)229.2 V1.33 V (0.58%)51.0 W✓ OK (≤3%)
70 mm²192 A150 A0.58 V (0.25%)229.4 V0.95 V (0.41%)36.4 W✓ OK (≤3%)
95 mm²232 A181 A0.43 V (0.19%)229.6 V0.7 V (0.31%)26.8 W✓ OK (≤3%)
120 mm²269 A210 A0.34 V (0.15%)229.7 V0.56 V (0.24%)21.2 W✓ OK (≤3%)
150 mm²309 A241 A0.27 V (0.12%)229.7 V0.44 V (0.19%)17.0 W✓ OK (≤3%)
185 mm²353 A275 A0.22 V (0.1%)229.8 V0.36 V (0.16%)13.8 W✓ OK (≤3%)
240 mm²415 A324 A0.17 V (0.07%)229.8 V0.28 V (0.12%)10.6 W✓ OK (≤3%)
300 mm²477 A372 A0.13 V (0.06%)229.9 V0.22 V (0.1%)8.5 W✓ OK (≤3%)
400 mm²570 A445 A0.1 V (0.04%)229.9 V0.17 V (0.07%)6.4 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 15 Meter (230V)

Vilken kabelarea krävs för 63A vid 15 meter (230V)?

För 63 Ampere över 15 meter vid 230V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (2.53V / 1.1%).

Hur stor effekt motsvarar 63A vid 230V?

Det motsvarar 14.49 kW med en rekommenderad säkring på 63A.