⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 175 Ampere vid 250 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 175 A över 250 m vid 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 10.81V (2.7%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 11.15V (2.79%)
Voltage at Load389.2 VLine Loss: 3276.9 W
Max Power & Breaker121.24 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1081.09 V (270.27%)0.0 V1783.29 V (445.82%)327687.5 WDrop High
2.5 mm²24 A18 A648.65 V (162.16%)0.0 V1069.97 V (267.49%)196612.5 WDrop High
4 mm²32 A25 A405.41 V (101.35%)0.0 V668.73 V (167.18%)122882.8 WDrop High
6 mm²41 A32 A270.27 V (67.57%)129.7 V445.82 V (111.46%)81921.9 WDrop High
10 mm²57 A44 A162.16 V (40.54%)237.8 V267.49 V (66.87%)49153.1 WDrop High
16 mm²76 A59 A101.35 V (25.34%)298.6 V167.18 V (41.8%)30720.7 WDrop High
25 mm²101 A78 A64.87 V (16.22%)335.1 V107.0 V (26.75%)19661.2 WDrop High
35 mm²125 A97 A46.33 V (11.58%)353.7 V76.43 V (19.11%)14043.8 WDrop High
50 mm²151 A118 A32.43 V (8.11%)367.6 V53.5 V (13.37%)9830.6 WDrop High
70 mm²192 A150 A23.17 V (5.79%)376.8 V38.21 V (9.55%)7021.9 WDrop High
95 mm²232 A181 A17.07 V (4.27%)382.9 V28.16 V (7.04%)5174.0 W~ ≤5%
120 mm²269 A210 A13.51 V (3.38%)386.5 V22.29 V (5.57%)4096.1 W~ ≤5%
150 mm²309 A241 A10.81 V (2.7%)389.2 V17.83 V (4.46%)3276.9 W✓ OK (≤3%)
185 mm²353 A275 A8.77 V (2.19%)391.2 V14.46 V (3.61%)2656.9 W✓ OK (≤3%)
240 mm²415 A324 A6.76 V (1.69%)393.2 V11.15 V (2.79%)2048.0 W✓ OK (≤3%)
300 mm²477 A372 A5.41 V (1.35%)394.6 V8.92 V (2.23%)1638.4 W✓ OK (≤3%)
400 mm²570 A445 A4.05 V (1.01%)395.9 V6.69 V (1.67%)1228.8 W✓ OK (≤3%)

FAQ — Kabelarea för 175 Ampere vid 250 Meter (400V)

Vilken kabelarea krävs för 175A vid 250 meter (400V)?

För 175 Ampere över 250 meter vid 400V rekommenderas 150 mm² kopparkabel för att hålla spänningsfallet under 3% (10.81V / 2.7%).

Hur stor effekt motsvarar 175A vid 400V?

Det motsvarar 121.24 kW med en rekommenderad säkring på 175A.