Kabelarea för 175 Ampere vid 10 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 175 A över 10 m vid 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 0.93V (0.23%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 1.13V (0.28%)
Voltage at Load399.1 VLine Loss: 280.9 W
Max Power & Breaker121.24 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A43.24 V (10.81%)356.8 V71.33 V (17.83%)13107.5 WDrop High
2.5 mm²24 A18 A25.95 V (6.49%)374.1 V42.8 V (10.7%)7864.5 WDrop High
4 mm²32 A25 A16.22 V (4.05%)383.8 V26.75 V (6.69%)4915.3 WDrop High
6 mm²41 A32 A10.81 V (2.7%)389.2 V17.83 V (4.46%)3276.9 WDrop High
10 mm²57 A44 A6.49 V (1.62%)393.5 V10.7 V (2.67%)1966.1 WDrop High
16 mm²76 A59 A4.05 V (1.01%)395.9 V6.69 V (1.67%)1228.8 WDrop High
25 mm²101 A78 A2.59 V (0.65%)397.4 V4.28 V (1.07%)786.5 WDrop High
35 mm²125 A97 A1.85 V (0.46%)398.1 V3.06 V (0.76%)561.8 WDrop High
50 mm²151 A118 A1.3 V (0.32%)398.7 V2.14 V (0.53%)393.2 WDrop High
70 mm²192 A150 A0.93 V (0.23%)399.1 V1.53 V (0.38%)280.9 W✓ OK (≤3%)
95 mm²232 A181 A0.68 V (0.17%)399.3 V1.13 V (0.28%)207.0 W✓ OK (≤3%)
120 mm²269 A210 A0.54 V (0.14%)399.5 V0.89 V (0.22%)163.8 W✓ OK (≤3%)
150 mm²309 A241 A0.43 V (0.11%)399.6 V0.71 V (0.18%)131.1 W✓ OK (≤3%)
185 mm²353 A275 A0.35 V (0.09%)399.6 V0.58 V (0.14%)106.3 W✓ OK (≤3%)
240 mm²415 A324 A0.27 V (0.07%)399.7 V0.45 V (0.11%)81.9 W✓ OK (≤3%)
300 mm²477 A372 A0.22 V (0.05%)399.8 V0.36 V (0.09%)65.5 W✓ OK (≤3%)
400 mm²570 A445 A0.16 V (0.04%)399.8 V0.27 V (0.07%)49.2 W✓ OK (≤3%)

FAQ — Kabelarea för 175 Ampere vid 10 Meter (400V)

Vilken kabelarea krävs för 175A vid 10 meter (400V)?

För 175 Ampere över 10 meter vid 400V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (0.93V / 0.23%).

Hur stor effekt motsvarar 175A vid 400V?

Det motsvarar 121.24 kW med en rekommenderad säkring på 175A.