Kabelarea för 20 Ampere vid 500 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 20 A över 500 m vid 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 10.59V (2.65%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 8.73V (2.18%)
Voltage at Load389.4 VLine Loss: 366.9 W
Max Power & Breaker13.86 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A247.11 V (61.78%)152.9 V407.61 V (101.9%)8560.0 WDrop High
2.5 mm²24 A18 A148.26 V (37.07%)251.7 V244.57 V (61.14%)5136.0 WDrop High
4 mm²32 A25 A92.66 V (23.17%)307.3 V152.85 V (38.21%)3210.0 WDrop High
6 mm²41 A32 A61.78 V (15.44%)338.2 V101.9 V (25.48%)2140.0 WDrop High
10 mm²57 A44 A37.07 V (9.27%)362.9 V61.14 V (15.29%)1284.0 WDrop High
16 mm²76 A59 A23.17 V (5.79%)376.8 V38.21 V (9.55%)802.5 WDrop High
25 mm²101 A78 A14.83 V (3.71%)385.2 V24.46 V (6.11%)513.6 W~ ≤5%
35 mm²125 A97 A10.59 V (2.65%)389.4 V17.47 V (4.37%)366.9 W✓ OK (≤3%)
50 mm²151 A118 A7.41 V (1.85%)392.6 V12.23 V (3.06%)256.8 W✓ OK (≤3%)
70 mm²192 A150 A5.3 V (1.32%)394.7 V8.73 V (2.18%)183.4 W✓ OK (≤3%)
95 mm²232 A181 A3.9 V (0.98%)396.1 V6.44 V (1.61%)135.2 W✓ OK (≤3%)
120 mm²269 A210 A3.09 V (0.77%)396.9 V5.1 V (1.27%)107.0 W✓ OK (≤3%)
150 mm²309 A241 A2.47 V (0.62%)397.5 V4.08 V (1.02%)85.6 W✓ OK (≤3%)
185 mm²353 A275 A2.0 V (0.5%)398.0 V3.3 V (0.83%)69.4 W✓ OK (≤3%)
240 mm²415 A324 A1.54 V (0.39%)398.5 V2.55 V (0.64%)53.5 W✓ OK (≤3%)
300 mm²477 A372 A1.24 V (0.31%)398.8 V2.04 V (0.51%)42.8 W✓ OK (≤3%)
400 mm²570 A445 A0.93 V (0.23%)399.1 V1.53 V (0.38%)32.1 W✓ OK (≤3%)

FAQ — Kabelarea för 20 Ampere vid 500 Meter (400V)

Vilken kabelarea krävs för 20A vid 500 meter (400V)?

För 20 Ampere över 500 meter vid 400V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (10.59V / 2.65%).

Hur stor effekt motsvarar 20A vid 400V?

Det motsvarar 13.86 kW med en rekommenderad säkring på 20A.