⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 40 Ampere vid 500 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 40 A över 500 m vid 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 10.59V (2.65%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 10.19V (2.55%)
Voltage at Load389.4 VLine Loss: 733.7 W
Max Power & Breaker27.71 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A494.21 V (123.55%)0.0 V815.22 V (203.8%)34240.0 WDrop High
2.5 mm²24 A18 A296.53 V (74.13%)103.5 V489.13 V (122.28%)20544.0 WDrop High
4 mm²32 A25 A185.33 V (46.33%)214.7 V305.71 V (76.43%)12840.0 WDrop High
6 mm²41 A32 A123.55 V (30.89%)276.4 V203.8 V (50.95%)8560.0 WDrop High
10 mm²57 A44 A74.13 V (18.53%)325.9 V122.28 V (30.57%)5136.0 WDrop High
16 mm²76 A59 A46.33 V (11.58%)353.7 V76.43 V (19.11%)3210.0 WDrop High
25 mm²101 A78 A29.65 V (7.41%)370.3 V48.91 V (12.23%)2054.4 WDrop High
35 mm²125 A97 A21.18 V (5.3%)378.8 V34.94 V (8.73%)1467.4 WDrop High
50 mm²151 A118 A14.83 V (3.71%)385.2 V24.46 V (6.11%)1027.2 W~ ≤5%
70 mm²192 A150 A10.59 V (2.65%)389.4 V17.47 V (4.37%)733.7 W✓ OK (≤3%)
95 mm²232 A181 A7.8 V (1.95%)392.2 V12.87 V (3.22%)540.6 W✓ OK (≤3%)
120 mm²269 A210 A6.18 V (1.54%)393.8 V10.19 V (2.55%)428.0 W✓ OK (≤3%)
150 mm²309 A241 A4.94 V (1.24%)395.1 V8.15 V (2.04%)342.4 W✓ OK (≤3%)
185 mm²353 A275 A4.01 V (1.0%)396.0 V6.61 V (1.65%)277.6 W✓ OK (≤3%)
240 mm²415 A324 A3.09 V (0.77%)396.9 V5.1 V (1.27%)214.0 W✓ OK (≤3%)
300 mm²477 A372 A2.47 V (0.62%)397.5 V4.08 V (1.02%)171.2 W✓ OK (≤3%)
400 mm²570 A445 A1.85 V (0.46%)398.1 V3.06 V (0.76%)128.4 W✓ OK (≤3%)

FAQ — Kabelarea för 40 Ampere vid 500 Meter (400V)

Vilken kabelarea krävs för 40A vid 500 meter (400V)?

För 40 Ampere över 500 meter vid 400V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (10.59V / 2.65%).

Hur stor effekt motsvarar 40A vid 400V?

Det motsvarar 27.71 kW med en rekommenderad säkring på 40A.