Kabelarea för 125 Ampere vid 500 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 125 A över 500 m vid 400V.

Copper Cable (≤3% Drop)240 mm²Drop: 9.65V (2.41%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.55V (2.39%)
Voltage at Load390.3 VLine Loss: 2089.8 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1544.41 V (386.1%)0.0 V2547.56 V (636.89%)334375.0 WDrop High
2.5 mm²24 A18 A926.65 V (231.66%)0.0 V1528.53 V (382.13%)200625.0 WDrop High
4 mm²32 A25 A579.15 V (144.79%)0.0 V955.33 V (238.83%)125390.6 WDrop High
6 mm²41 A32 A386.1 V (96.53%)13.9 V636.89 V (159.22%)83593.8 WDrop High
10 mm²57 A44 A231.66 V (57.92%)168.3 V382.13 V (95.53%)50156.2 WDrop High
16 mm²76 A59 A144.79 V (36.2%)255.2 V238.83 V (59.71%)31347.7 WDrop High
25 mm²101 A78 A92.66 V (23.17%)307.3 V152.85 V (38.21%)20062.5 WDrop High
35 mm²125 A97 A66.19 V (16.55%)333.8 V109.18 V (27.3%)14330.4 WDrop High
50 mm²151 A118 A46.33 V (11.58%)353.7 V76.43 V (19.11%)10031.2 WDrop High
70 mm²192 A150 A33.09 V (8.27%)366.9 V54.59 V (13.65%)7165.2 WDrop High
95 mm²232 A181 A24.39 V (6.1%)375.6 V40.22 V (10.06%)5279.6 WDrop High
120 mm²269 A210 A19.31 V (4.83%)380.7 V31.84 V (7.96%)4179.7 W~ ≤5%
150 mm²309 A241 A15.44 V (3.86%)384.6 V25.48 V (6.37%)3343.8 W~ ≤5%
185 mm²353 A275 A12.52 V (3.13%)387.5 V20.66 V (5.16%)2711.1 W~ ≤5%
240 mm²415 A324 A9.65 V (2.41%)390.3 V15.92 V (3.98%)2089.8 W✓ OK (≤3%)
300 mm²477 A372 A7.72 V (1.93%)392.3 V12.74 V (3.18%)1671.9 W✓ OK (≤3%)
400 mm²570 A445 A5.79 V (1.45%)394.2 V9.55 V (2.39%)1253.9 W✓ OK (≤3%)

FAQ — Kabelarea för 125 Ampere vid 500 Meter (400V)

Vilken kabelarea krävs för 125A vid 500 meter (400V)?

För 125 Ampere över 500 meter vid 400V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (9.65V / 2.41%).

Hur stor effekt motsvarar 125A vid 400V?

Det motsvarar 86.6 kW med en rekommenderad säkring på 125A.