Kabelarea för 125 Ampere vid 500 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 125 A över 500 m vid 400V.
Copper Cable (≤3% Drop)240 mm²Drop: 9.65V (2.41%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.55V (2.39%)
Voltage at Load390.3 VLine Loss: 2089.8 W
Max Power & Breaker86.6 kW125A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 500m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1544.41 V (386.1%) | 0.0 V | 2547.56 V (636.89%) | 334375.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 926.65 V (231.66%) | 0.0 V | 1528.53 V (382.13%) | 200625.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 579.15 V (144.79%) | 0.0 V | 955.33 V (238.83%) | 125390.6 W | Drop High |
| 6 mm² | 41 A | 32 A | 386.1 V (96.53%) | 13.9 V | 636.89 V (159.22%) | 83593.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 231.66 V (57.92%) | 168.3 V | 382.13 V (95.53%) | 50156.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 144.79 V (36.2%) | 255.2 V | 238.83 V (59.71%) | 31347.7 W | Drop High |
| 25 mm² | 101 A | 78 A | 92.66 V (23.17%) | 307.3 V | 152.85 V (38.21%) | 20062.5 W | Drop High |
| 35 mm² | 125 A | 97 A | 66.19 V (16.55%) | 333.8 V | 109.18 V (27.3%) | 14330.4 W | Drop High |
| 50 mm² | 151 A | 118 A | 46.33 V (11.58%) | 353.7 V | 76.43 V (19.11%) | 10031.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 33.09 V (8.27%) | 366.9 V | 54.59 V (13.65%) | 7165.2 W | Drop High |
| 95 mm² | 232 A | 181 A | 24.39 V (6.1%) | 375.6 V | 40.22 V (10.06%) | 5279.6 W | Drop High |
| 120 mm² | 269 A | 210 A | 19.31 V (4.83%) | 380.7 V | 31.84 V (7.96%) | 4179.7 W | ~ ≤5% |
| 150 mm² | 309 A | 241 A | 15.44 V (3.86%) | 384.6 V | 25.48 V (6.37%) | 3343.8 W | ~ ≤5% |
| 185 mm² | 353 A | 275 A | 12.52 V (3.13%) | 387.5 V | 20.66 V (5.16%) | 2711.1 W | ~ ≤5% |
| 240 mm² | 415 A | 324 A | 9.65 V (2.41%) | 390.3 V | 15.92 V (3.98%) | 2089.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 7.72 V (1.93%) | 392.3 V | 12.74 V (3.18%) | 1671.9 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 5.79 V (1.45%) | 394.2 V | 9.55 V (2.39%) | 1253.9 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 125 Ampere vid 500 Meter (400V)
Vilken kabelarea krävs för 125A vid 500 meter (400V)?
För 125 Ampere över 500 meter vid 400V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (9.65V / 2.41%).
Hur stor effekt motsvarar 125A vid 400V?
Det motsvarar 86.6 kW med en rekommenderad säkring på 125A.
Related Lengths & Currents (400V)
125A · 5m (400V)125A · 10m (400V)125A · 15m (400V)125A · 20m (400V)125A · 25m (400V)125A · 30m (400V)125A · 35m (400V)125A · 40m (400V)125A · 45m (400V)125A · 50m (400V)125A · 60m (400V)125A · 70m (400V)10A · 500m (400V)16A · 500m (400V)20A · 500m (400V)25A · 500m (400V)32A · 500m (400V)40A · 500m (400V)50A · 500m (400V)63A · 500m (400V)80A · 500m (400V)100A · 500m (400V)160A · 500m (400V)200A · 500m (400V)