Kabelarea för 250 Ampere vid 250 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 250 A över 250 m vid 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 6.69V (2.91%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.03V (4.8%)
Voltage at Load223.3 VLine Loss: 1671.9 W
Max Power & Breaker57.5 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1783.33 V (775.36%)0.0 V2941.67 V (1278.99%)445833.3 WDrop High
2.5 mm²24 A18 A1070.0 V (465.22%)0.0 V1765.0 V (767.39%)267500.0 WDrop High
4 mm²32 A25 A668.75 V (290.76%)0.0 V1103.12 V (479.62%)167187.5 WDrop High
6 mm²41 A32 A445.83 V (193.84%)0.0 V735.42 V (319.75%)111458.3 WDrop High
10 mm²57 A44 A267.5 V (116.3%)0.0 V441.25 V (191.85%)66875.0 WDrop High
16 mm²76 A59 A167.19 V (72.69%)62.8 V275.78 V (119.9%)41796.9 WDrop High
25 mm²101 A78 A107.0 V (46.52%)123.0 V176.5 V (76.74%)26750.0 WDrop High
35 mm²125 A97 A76.43 V (33.23%)153.6 V126.07 V (54.81%)19107.1 WDrop High
50 mm²151 A118 A53.5 V (23.26%)176.5 V88.25 V (38.37%)13375.0 WDrop High
70 mm²192 A150 A38.21 V (16.61%)191.8 V63.04 V (27.41%)9553.6 WDrop High
95 mm²232 A181 A28.16 V (12.24%)201.8 V46.45 V (20.19%)7039.5 WDrop High
120 mm²269 A210 A22.29 V (9.69%)207.7 V36.77 V (15.99%)5572.9 WDrop High
150 mm²309 A241 A17.83 V (7.75%)212.2 V29.42 V (12.79%)4458.3 WDrop High
185 mm²353 A275 A14.46 V (6.29%)215.5 V23.85 V (10.37%)3614.9 WDrop High
240 mm²415 A324 A11.15 V (4.85%)218.9 V18.39 V (7.99%)2786.5 W~ ≤5%
300 mm²477 A372 A8.92 V (3.88%)221.1 V14.71 V (6.39%)2229.2 W~ ≤5%
400 mm²570 A445 A6.69 V (2.91%)223.3 V11.03 V (4.8%)1671.9 W✓ OK (≤3%)

FAQ — Kabelarea för 250 Ampere vid 250 Meter (230V)

Vilken kabelarea krävs för 250A vid 250 meter (230V)?

För 250 Ampere över 250 meter vid 230V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.69V / 2.91%).

Hur stor effekt motsvarar 250A vid 230V?

Det motsvarar 57.5 kW med en rekommenderad säkring på 250A.