Kabelarea för 275 Ampere vid 175 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 275 A över 175 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 6.87V (2.99%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.49V (3.69%)
Voltage at Load223.1 VLine Loss: 1888.1 W
Max Power & Breaker63.25 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 275A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1373.17 V (597.03%)0.0 V2265.08 V (984.82%)377620.8 WDrop High
2.5 mm²24 A18 A823.9 V (358.22%)0.0 V1359.05 V (590.89%)226572.5 WDrop High
4 mm²32 A25 A514.94 V (223.89%)0.0 V849.41 V (369.31%)141607.8 WDrop High
6 mm²41 A32 A343.29 V (149.26%)0.0 V566.27 V (246.2%)94405.2 WDrop High
10 mm²57 A44 A205.97 V (89.55%)24.0 V339.76 V (147.72%)56643.1 WDrop High
16 mm²76 A59 A128.73 V (55.97%)101.3 V212.35 V (92.33%)35402.0 WDrop High
25 mm²101 A78 A82.39 V (35.82%)147.6 V135.91 V (59.09%)22657.2 WDrop High
35 mm²125 A97 A58.85 V (25.59%)171.2 V97.07 V (42.21%)16183.7 WDrop High
50 mm²151 A118 A41.2 V (17.91%)188.8 V67.95 V (29.54%)11328.6 WDrop High
70 mm²192 A150 A29.42 V (12.79%)200.6 V48.54 V (21.1%)8091.9 WDrop High
95 mm²232 A181 A21.68 V (9.43%)208.3 V35.76 V (15.55%)5962.4 WDrop High
120 mm²269 A210 A17.16 V (7.46%)212.8 V28.31 V (12.31%)4720.3 WDrop High
150 mm²309 A241 A13.73 V (5.97%)216.3 V22.65 V (9.85%)3776.2 WDrop High
185 mm²353 A275 A11.13 V (4.84%)218.9 V18.37 V (7.99%)3061.8 W~ ≤5%
240 mm²415 A324 A8.58 V (3.73%)221.4 V14.16 V (6.16%)2360.1 W~ ≤5%
300 mm²477 A372 A6.87 V (2.99%)223.1 V11.33 V (4.92%)1888.1 W✓ OK (≤3%)
400 mm²570 A445 A5.15 V (2.24%)224.9 V8.49 V (3.69%)1416.1 W✓ OK (≤3%)

FAQ — Kabelarea för 275 Ampere vid 175 Meter (230V)

Vilken kabelarea krävs för 275A vid 175 meter (230V)?

För 275 Ampere över 175 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (6.87V / 2.99%).

Hur stor effekt motsvarar 275A vid 230V?

Det motsvarar 63.25 kW med en rekommenderad säkring på 300A.