Kabelarea för 275 Ampere vid 175 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 275 A över 175 m vid 230V.
Copper Cable (≤3% Drop)300 mm²Drop: 6.87V (2.99%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.49V (3.69%)
Voltage at Load223.1 VLine Loss: 1888.1 W
Max Power & Breaker63.25 kW300A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 275A at 175m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1373.17 V (597.03%) | 0.0 V | 2265.08 V (984.82%) | 377620.8 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 823.9 V (358.22%) | 0.0 V | 1359.05 V (590.89%) | 226572.5 W | Drop High |
| 4 mm² | 32 A | 25 A | 514.94 V (223.89%) | 0.0 V | 849.41 V (369.31%) | 141607.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 343.29 V (149.26%) | 0.0 V | 566.27 V (246.2%) | 94405.2 W | Drop High |
| 10 mm² | 57 A | 44 A | 205.97 V (89.55%) | 24.0 V | 339.76 V (147.72%) | 56643.1 W | Drop High |
| 16 mm² | 76 A | 59 A | 128.73 V (55.97%) | 101.3 V | 212.35 V (92.33%) | 35402.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 82.39 V (35.82%) | 147.6 V | 135.91 V (59.09%) | 22657.2 W | Drop High |
| 35 mm² | 125 A | 97 A | 58.85 V (25.59%) | 171.2 V | 97.07 V (42.21%) | 16183.7 W | Drop High |
| 50 mm² | 151 A | 118 A | 41.2 V (17.91%) | 188.8 V | 67.95 V (29.54%) | 11328.6 W | Drop High |
| 70 mm² | 192 A | 150 A | 29.42 V (12.79%) | 200.6 V | 48.54 V (21.1%) | 8091.9 W | Drop High |
| 95 mm² | 232 A | 181 A | 21.68 V (9.43%) | 208.3 V | 35.76 V (15.55%) | 5962.4 W | Drop High |
| 120 mm² | 269 A | 210 A | 17.16 V (7.46%) | 212.8 V | 28.31 V (12.31%) | 4720.3 W | Drop High |
| 150 mm² | 309 A | 241 A | 13.73 V (5.97%) | 216.3 V | 22.65 V (9.85%) | 3776.2 W | Drop High |
| 185 mm² | 353 A | 275 A | 11.13 V (4.84%) | 218.9 V | 18.37 V (7.99%) | 3061.8 W | ~ ≤5% |
| 240 mm² | 415 A | 324 A | 8.58 V (3.73%) | 221.4 V | 14.16 V (6.16%) | 2360.1 W | ~ ≤5% |
| 300 mm² | 477 A | 372 A | 6.87 V (2.99%) | 223.1 V | 11.33 V (4.92%) | 1888.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 5.15 V (2.24%) | 224.9 V | 8.49 V (3.69%) | 1416.1 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 275 Ampere vid 175 Meter (230V)
Vilken kabelarea krävs för 275A vid 175 meter (230V)?
För 275 Ampere över 175 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (6.87V / 2.99%).
Hur stor effekt motsvarar 275A vid 230V?
Det motsvarar 63.25 kW med en rekommenderad säkring på 300A.
Related Lengths & Currents (230V)
275A · 5m (230V)275A · 10m (230V)275A · 15m (230V)275A · 20m (230V)275A · 25m (230V)275A · 30m (230V)275A · 35m (230V)275A · 40m (230V)275A · 45m (230V)275A · 50m (230V)275A · 60m (230V)275A · 70m (230V)10A · 175m (230V)16A · 175m (230V)20A · 175m (230V)25A · 175m (230V)32A · 175m (230V)40A · 175m (230V)50A · 175m (230V)63A · 175m (230V)80A · 175m (230V)100A · 175m (230V)125A · 175m (230V)160A · 175m (230V)200A · 175m (230V)