Kabelarea för 275 Ampere vid 5 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 275 A över 5 m vid 230V.
Copper Cable (≤3% Drop)150 mm²Drop: 0.39V (0.17%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 0.52V (0.23%)
Voltage at Load229.6 VLine Loss: 107.9 W
Max Power & Breaker63.25 kW300A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 275A at 5m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 39.23 V (17.06%) | 190.8 V | 64.72 V (28.14%) | 10789.2 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 23.54 V (10.23%) | 206.5 V | 38.83 V (16.88%) | 6473.5 W | Drop High |
| 4 mm² | 32 A | 25 A | 14.71 V (6.4%) | 215.3 V | 24.27 V (10.55%) | 4045.9 W | Drop High |
| 6 mm² | 41 A | 32 A | 9.81 V (4.26%) | 220.2 V | 16.18 V (7.03%) | 2697.3 W | Drop High |
| 10 mm² | 57 A | 44 A | 5.88 V (2.56%) | 224.1 V | 9.71 V (4.22%) | 1618.4 W | Drop High |
| 16 mm² | 76 A | 59 A | 3.68 V (1.6%) | 226.3 V | 6.07 V (2.64%) | 1011.5 W | Drop High |
| 25 mm² | 101 A | 78 A | 2.35 V (1.02%) | 227.6 V | 3.88 V (1.69%) | 647.4 W | Drop High |
| 35 mm² | 125 A | 97 A | 1.68 V (0.73%) | 228.3 V | 2.77 V (1.21%) | 462.4 W | Drop High |
| 50 mm² | 151 A | 118 A | 1.18 V (0.51%) | 228.8 V | 1.94 V (0.84%) | 323.7 W | Drop High |
| 70 mm² | 192 A | 150 A | 0.84 V (0.37%) | 229.2 V | 1.39 V (0.6%) | 231.2 W | Drop High |
| 95 mm² | 232 A | 181 A | 0.62 V (0.27%) | 229.4 V | 1.02 V (0.44%) | 170.4 W | Drop High |
| 120 mm² | 269 A | 210 A | 0.49 V (0.21%) | 229.5 V | 0.81 V (0.35%) | 134.9 W | Drop High |
| 150 mm² | 309 A | 241 A | 0.39 V (0.17%) | 229.6 V | 0.65 V (0.28%) | 107.9 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.32 V (0.14%) | 229.7 V | 0.52 V (0.23%) | 87.5 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.25 V (0.11%) | 229.8 V | 0.4 V (0.18%) | 67.4 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.2 V (0.09%) | 229.8 V | 0.32 V (0.14%) | 53.9 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.15 V (0.06%) | 229.9 V | 0.24 V (0.11%) | 40.5 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 275 Ampere vid 5 Meter (230V)
Vilken kabelarea krävs för 275A vid 5 meter (230V)?
För 275 Ampere över 5 meter vid 230V rekommenderas 150 mm² kopparkabel för att hålla spänningsfallet under 3% (0.39V / 0.17%).
Hur stor effekt motsvarar 275A vid 230V?
Det motsvarar 63.25 kW med en rekommenderad säkring på 300A.
Related Lengths & Currents (230V)
275A · 10m (230V)275A · 15m (230V)275A · 20m (230V)275A · 25m (230V)275A · 30m (230V)275A · 35m (230V)275A · 40m (230V)275A · 45m (230V)275A · 50m (230V)275A · 60m (230V)275A · 70m (230V)10A · 5m (230V)16A · 5m (230V)20A · 5m (230V)25A · 5m (230V)32A · 5m (230V)40A · 5m (230V)50A · 5m (230V)63A · 5m (230V)80A · 5m (230V)100A · 5m (230V)125A · 5m (230V)160A · 5m (230V)200A · 5m (230V)