Kabelarea för 275 Ampere vid 80 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 275 A över 80 m vid 230V.

Copper Cable (≤3% Drop)150 mm²Drop: 6.28V (2.73%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 6.47V (2.81%)
Voltage at Load223.7 VLine Loss: 1726.3 W
Max Power & Breaker63.25 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 275A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A627.73 V (272.93%)0.0 V1035.47 V (450.2%)172626.7 WDrop High
2.5 mm²24 A18 A376.64 V (163.76%)0.0 V621.28 V (270.12%)103576.0 WDrop High
4 mm²32 A25 A235.4 V (102.35%)0.0 V388.3 V (168.83%)64735.0 WDrop High
6 mm²41 A32 A156.93 V (68.23%)73.1 V258.87 V (112.55%)43156.7 WDrop High
10 mm²57 A44 A94.16 V (40.94%)135.8 V155.32 V (67.53%)25894.0 WDrop High
16 mm²76 A59 A58.85 V (25.59%)171.2 V97.07 V (42.21%)16183.8 WDrop High
25 mm²101 A78 A37.66 V (16.38%)192.3 V62.13 V (27.01%)10357.6 WDrop High
35 mm²125 A97 A26.9 V (11.7%)203.1 V44.38 V (19.29%)7398.3 WDrop High
50 mm²151 A118 A18.83 V (8.19%)211.2 V31.06 V (13.51%)5178.8 WDrop High
70 mm²192 A150 A13.45 V (5.85%)216.5 V22.19 V (9.65%)3699.1 WDrop High
95 mm²232 A181 A9.91 V (4.31%)220.1 V16.35 V (7.11%)2725.7 WDrop High
120 mm²269 A210 A7.85 V (3.41%)222.2 V12.94 V (5.63%)2157.8 WDrop High
150 mm²309 A241 A6.28 V (2.73%)223.7 V10.35 V (4.5%)1726.3 W✓ OK (≤3%)
185 mm²353 A275 A5.09 V (2.21%)224.9 V8.4 V (3.65%)1399.7 W✓ OK (≤3%)
240 mm²415 A324 A3.92 V (1.71%)226.1 V6.47 V (2.81%)1078.9 W✓ OK (≤3%)
300 mm²477 A372 A3.14 V (1.36%)226.9 V5.18 V (2.25%)863.1 W✓ OK (≤3%)
400 mm²570 A445 A2.35 V (1.02%)227.6 V3.88 V (1.69%)647.4 W✓ OK (≤3%)

FAQ — Kabelarea för 275 Ampere vid 80 Meter (230V)

Vilken kabelarea krävs för 275A vid 80 meter (230V)?

För 275 Ampere över 80 meter vid 230V rekommenderas 150 mm² kopparkabel för att hålla spänningsfallet under 3% (6.28V / 2.73%).

Hur stor effekt motsvarar 275A vid 230V?

Det motsvarar 63.25 kW med en rekommenderad säkring på 300A.