Kabelarea för 350 Ampere vid 10 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 350 A över 10 m vid 230V.

Copper Cable (≤3% Drop)185 mm²Drop: 0.81V (0.35%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 0.82V (0.36%)
Voltage at Load229.2 VLine Loss: 283.4 W
Max Power & Breaker80.5 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A99.87 V (43.42%)130.1 V164.73 V (71.62%)34953.3 WDrop High
2.5 mm²24 A18 A59.92 V (26.05%)170.1 V98.84 V (42.97%)20972.0 WDrop High
4 mm²32 A25 A37.45 V (16.28%)192.6 V61.77 V (26.86%)13107.5 WDrop High
6 mm²41 A32 A24.97 V (10.86%)205.0 V41.18 V (17.91%)8738.3 WDrop High
10 mm²57 A44 A14.98 V (6.51%)215.0 V24.71 V (10.74%)5243.0 WDrop High
16 mm²76 A59 A9.36 V (4.07%)220.6 V15.44 V (6.71%)3276.9 WDrop High
25 mm²101 A78 A5.99 V (2.61%)224.0 V9.88 V (4.3%)2097.2 WDrop High
35 mm²125 A97 A4.28 V (1.86%)225.7 V7.06 V (3.07%)1498.0 WDrop High
50 mm²151 A118 A3.0 V (1.3%)227.0 V4.94 V (2.15%)1048.6 WDrop High
70 mm²192 A150 A2.14 V (0.93%)227.9 V3.53 V (1.53%)749.0 WDrop High
95 mm²232 A181 A1.58 V (0.69%)228.4 V2.6 V (1.13%)551.9 WDrop High
120 mm²269 A210 A1.25 V (0.54%)228.8 V2.06 V (0.9%)436.9 WDrop High
150 mm²309 A241 A1.0 V (0.43%)229.0 V1.65 V (0.72%)349.5 WDrop High
185 mm²353 A275 A0.81 V (0.35%)229.2 V1.34 V (0.58%)283.4 W✓ OK (≤3%)
240 mm²415 A324 A0.62 V (0.27%)229.4 V1.03 V (0.45%)218.5 W✓ OK (≤3%)
300 mm²477 A372 A0.5 V (0.22%)229.5 V0.82 V (0.36%)174.8 W✓ OK (≤3%)
400 mm²570 A445 A0.37 V (0.16%)229.6 V0.62 V (0.27%)131.1 W✓ OK (≤3%)

FAQ — Kabelarea för 350 Ampere vid 10 Meter (230V)

Vilken kabelarea krävs för 350A vid 10 meter (230V)?

För 350 Ampere över 10 meter vid 230V rekommenderas 185 mm² kopparkabel för att hålla spänningsfallet under 3% (0.81V / 0.35%).

Hur stor effekt motsvarar 350A vid 230V?

Det motsvarar 80.5 kW med en rekommenderad säkring på 350A.