⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 350 Ampere vid 25 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 350 A över 25 m vid 230V.

Copper Cable (≤3% Drop)185 mm²Drop: 2.02V (0.88%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 2.06V (0.9%)
Voltage at Load228.0 VLine Loss: 708.5 W
Max Power & Breaker80.5 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A249.67 V (108.55%)0.0 V411.83 V (179.06%)87383.3 WDrop High
2.5 mm²24 A18 A149.8 V (65.13%)80.2 V247.1 V (107.43%)52430.0 WDrop High
4 mm²32 A25 A93.62 V (40.71%)136.4 V154.44 V (67.15%)32768.7 WDrop High
6 mm²41 A32 A62.42 V (27.14%)167.6 V102.96 V (44.76%)21845.8 WDrop High
10 mm²57 A44 A37.45 V (16.28%)192.6 V61.77 V (26.86%)13107.5 WDrop High
16 mm²76 A59 A23.41 V (10.18%)206.6 V38.61 V (16.79%)8192.2 WDrop High
25 mm²101 A78 A14.98 V (6.51%)215.0 V24.71 V (10.74%)5243.0 WDrop High
35 mm²125 A97 A10.7 V (4.65%)219.3 V17.65 V (7.67%)3745.0 WDrop High
50 mm²151 A118 A7.49 V (3.26%)222.5 V12.35 V (5.37%)2621.5 WDrop High
70 mm²192 A150 A5.35 V (2.33%)224.7 V8.82 V (3.84%)1872.5 WDrop High
95 mm²232 A181 A3.94 V (1.71%)226.1 V6.5 V (2.83%)1379.7 WDrop High
120 mm²269 A210 A3.12 V (1.36%)226.9 V5.15 V (2.24%)1092.3 WDrop High
150 mm²309 A241 A2.5 V (1.09%)227.5 V4.12 V (1.79%)873.8 WDrop High
185 mm²353 A275 A2.02 V (0.88%)228.0 V3.34 V (1.45%)708.5 W✓ OK (≤3%)
240 mm²415 A324 A1.56 V (0.68%)228.4 V2.57 V (1.12%)546.1 W✓ OK (≤3%)
300 mm²477 A372 A1.25 V (0.54%)228.8 V2.06 V (0.9%)436.9 W✓ OK (≤3%)
400 mm²570 A445 A0.94 V (0.41%)229.1 V1.54 V (0.67%)327.7 W✓ OK (≤3%)

FAQ — Kabelarea för 350 Ampere vid 25 Meter (230V)

Vilken kabelarea krävs för 350A vid 25 meter (230V)?

För 350 Ampere över 25 meter vid 230V rekommenderas 185 mm² kopparkabel för att hålla spänningsfallet under 3% (2.02V / 0.88%).

Hur stor effekt motsvarar 350A vid 230V?

Det motsvarar 80.5 kW med en rekommenderad säkring på 350A.