Kabelarea för 375 Ampere vid 35 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 375 A över 35 m vid 400V.

Copper Cable (≤3% Drop)240 mm²Drop: 2.03V (0.51%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.01V (0.5%)
Voltage at Load398.0 VLine Loss: 1316.6 W
Max Power & Breaker259.81 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A324.33 V (81.08%)75.7 V534.99 V (133.75%)210656.2 WDrop High
2.5 mm²24 A18 A194.6 V (48.65%)205.4 V320.99 V (80.25%)126393.7 WDrop High
4 mm²32 A25 A121.62 V (30.41%)278.4 V200.62 V (50.16%)78996.1 WDrop High
6 mm²41 A32 A81.08 V (20.27%)318.9 V133.75 V (33.44%)52664.1 WDrop High
10 mm²57 A44 A48.65 V (12.16%)351.4 V80.25 V (20.06%)31598.4 WDrop High
16 mm²76 A59 A30.41 V (7.6%)369.6 V50.16 V (12.54%)19749.0 WDrop High
25 mm²101 A78 A19.46 V (4.86%)380.5 V32.1 V (8.02%)12639.4 WDrop High
35 mm²125 A97 A13.9 V (3.47%)386.1 V22.93 V (5.73%)9028.1 WDrop High
50 mm²151 A118 A9.73 V (2.43%)390.3 V16.05 V (4.01%)6319.7 WDrop High
70 mm²192 A150 A6.95 V (1.74%)393.1 V11.46 V (2.87%)4514.1 WDrop High
95 mm²232 A181 A5.12 V (1.28%)394.9 V8.45 V (2.11%)3326.2 WDrop High
120 mm²269 A210 A4.05 V (1.01%)395.9 V6.69 V (1.67%)2633.2 WDrop High
150 mm²309 A241 A3.24 V (0.81%)396.8 V5.35 V (1.34%)2106.6 WDrop High
185 mm²353 A275 A2.63 V (0.66%)397.4 V4.34 V (1.08%)1708.0 WDrop High
240 mm²415 A324 A2.03 V (0.51%)398.0 V3.34 V (0.84%)1316.6 W✓ OK (≤3%)
300 mm²477 A372 A1.62 V (0.41%)398.4 V2.67 V (0.67%)1053.3 W✓ OK (≤3%)
400 mm²570 A445 A1.22 V (0.3%)398.8 V2.01 V (0.5%)790.0 W✓ OK (≤3%)

FAQ — Kabelarea för 375 Ampere vid 35 Meter (400V)

Vilken kabelarea krävs för 375A vid 35 meter (400V)?

För 375 Ampere över 35 meter vid 400V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (2.03V / 0.51%).

Hur stor effekt motsvarar 375A vid 400V?

Det motsvarar 259.81 kW med en rekommenderad säkring på 400A.