⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 375 Ampere vid 50 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 375 A över 50 m vid 400V.

Copper Cable (≤3% Drop)240 mm²Drop: 2.9V (0.72%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.87V (0.72%)
Voltage at Load397.1 VLine Loss: 1880.9 W
Max Power & Breaker259.81 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A463.32 V (115.83%)0.0 V764.27 V (191.07%)300937.5 WDrop High
2.5 mm²24 A18 A277.99 V (69.5%)122.0 V458.56 V (114.64%)180562.5 WDrop High
4 mm²32 A25 A173.75 V (43.44%)226.3 V286.6 V (71.65%)112851.6 WDrop High
6 mm²41 A32 A115.83 V (28.96%)284.2 V191.07 V (47.77%)75234.4 WDrop High
10 mm²57 A44 A69.5 V (17.37%)330.5 V114.64 V (28.66%)45140.6 WDrop High
16 mm²76 A59 A43.44 V (10.86%)356.6 V71.65 V (17.91%)28212.9 WDrop High
25 mm²101 A78 A27.8 V (6.95%)372.2 V45.86 V (11.46%)18056.2 WDrop High
35 mm²125 A97 A19.86 V (4.96%)380.1 V32.75 V (8.19%)12897.3 WDrop High
50 mm²151 A118 A13.9 V (3.47%)386.1 V22.93 V (5.73%)9028.1 WDrop High
70 mm²192 A150 A9.93 V (2.48%)390.1 V16.38 V (4.09%)6448.7 WDrop High
95 mm²232 A181 A7.32 V (1.83%)392.7 V12.07 V (3.02%)4751.6 WDrop High
120 mm²269 A210 A5.79 V (1.45%)394.2 V9.55 V (2.39%)3761.7 WDrop High
150 mm²309 A241 A4.63 V (1.16%)395.4 V7.64 V (1.91%)3009.4 WDrop High
185 mm²353 A275 A3.76 V (0.94%)396.2 V6.2 V (1.55%)2440.0 WDrop High
240 mm²415 A324 A2.9 V (0.72%)397.1 V4.78 V (1.19%)1880.9 W✓ OK (≤3%)
300 mm²477 A372 A2.32 V (0.58%)397.7 V3.82 V (0.96%)1504.7 W✓ OK (≤3%)
400 mm²570 A445 A1.74 V (0.43%)398.3 V2.87 V (0.72%)1128.5 W✓ OK (≤3%)

FAQ — Kabelarea för 375 Ampere vid 50 Meter (400V)

Vilken kabelarea krävs för 375A vid 50 meter (400V)?

För 375 Ampere över 50 meter vid 400V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (2.9V / 0.72%).

Hur stor effekt motsvarar 375A vid 400V?

Det motsvarar 259.81 kW med en rekommenderad säkring på 400A.