Kabelarea för 375 Ampere vid 400 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 375 A över 400 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.95V (1.74%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 22.93V (5.73%)
Voltage at Load393.1 VLine Loss: 4514.1 W
Max Power & Breaker259.81 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3706.59 V (926.65%)0.0 V6114.14 V (1528.53%)2407500.0 WDrop High
2.5 mm²24 A18 A2223.95 V (555.99%)0.0 V3668.48 V (917.12%)1444500.0 WDrop High
4 mm²32 A25 A1389.97 V (347.49%)0.0 V2292.8 V (573.2%)902812.5 WDrop High
6 mm²41 A32 A926.65 V (231.66%)0.0 V1528.53 V (382.13%)601875.0 WDrop High
10 mm²57 A44 A555.99 V (139.0%)0.0 V917.12 V (229.28%)361125.0 WDrop High
16 mm²76 A59 A347.49 V (86.87%)52.5 V573.2 V (143.3%)225703.1 WDrop High
25 mm²101 A78 A222.4 V (55.6%)177.6 V366.85 V (91.71%)144450.0 WDrop High
35 mm²125 A97 A158.85 V (39.71%)241.1 V262.03 V (65.51%)103178.6 WDrop High
50 mm²151 A118 A111.2 V (27.8%)288.8 V183.42 V (45.86%)72225.0 WDrop High
70 mm²192 A150 A79.43 V (19.86%)320.6 V131.02 V (32.75%)51589.3 WDrop High
95 mm²232 A181 A58.53 V (14.63%)341.5 V96.54 V (24.13%)38013.2 WDrop High
120 mm²269 A210 A46.33 V (11.58%)353.7 V76.43 V (19.11%)30093.7 WDrop High
150 mm²309 A241 A37.07 V (9.27%)362.9 V61.14 V (15.29%)24075.0 WDrop High
185 mm²353 A275 A30.05 V (7.51%)369.9 V49.57 V (12.39%)19520.3 WDrop High
240 mm²415 A324 A23.17 V (5.79%)376.8 V38.21 V (9.55%)15046.9 WDrop High
300 mm²477 A372 A18.53 V (4.63%)381.5 V30.57 V (7.64%)12037.5 W~ ≤5%
400 mm²570 A445 A13.9 V (3.47%)386.1 V22.93 V (5.73%)9028.1 W~ ≤5%

FAQ — Kabelarea för 375 Ampere vid 400 Meter (400V)

Vilken kabelarea krävs för 375A vid 400 meter (400V)?

För 375 Ampere över 400 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.95V / 1.74%).

Hur stor effekt motsvarar 375A vid 400V?

Det motsvarar 259.81 kW med en rekommenderad säkring på 400A.