Kabelarea för 40 Ampere vid 40 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 40 A över 40 m vid 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 4.52V (1.96%)
Voltage at Load223.2 VLine Loss: 273.9 W
Max Power & Breaker9.2 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A45.65 V (19.85%)184.3 V75.31 V (32.74%)1826.1 WDrop High
2.5 mm²24 A18 A27.39 V (11.91%)202.6 V45.18 V (19.65%)1095.7 WDrop High
4 mm²32 A25 A17.12 V (7.44%)212.9 V28.24 V (12.28%)684.8 WDrop High
6 mm²41 A32 A11.41 V (4.96%)218.6 V18.83 V (8.19%)456.5 W~ ≤5%
10 mm²57 A44 A6.85 V (2.98%)223.2 V11.3 V (4.91%)273.9 W✓ OK (≤3%)
16 mm²76 A59 A4.28 V (1.86%)225.7 V7.06 V (3.07%)171.2 W✓ OK (≤3%)
25 mm²101 A78 A2.74 V (1.19%)227.3 V4.52 V (1.96%)109.6 W✓ OK (≤3%)
35 mm²125 A97 A1.96 V (0.85%)228.0 V3.23 V (1.4%)78.3 W✓ OK (≤3%)
50 mm²151 A118 A1.37 V (0.6%)228.6 V2.26 V (0.98%)54.8 W✓ OK (≤3%)
70 mm²192 A150 A0.98 V (0.43%)229.0 V1.61 V (0.7%)39.1 W✓ OK (≤3%)
95 mm²232 A181 A0.72 V (0.31%)229.3 V1.19 V (0.52%)28.8 W✓ OK (≤3%)
120 mm²269 A210 A0.57 V (0.25%)229.4 V0.94 V (0.41%)22.8 W✓ OK (≤3%)
150 mm²309 A241 A0.46 V (0.2%)229.5 V0.75 V (0.33%)18.3 W✓ OK (≤3%)
185 mm²353 A275 A0.37 V (0.16%)229.6 V0.61 V (0.27%)14.8 W✓ OK (≤3%)
240 mm²415 A324 A0.29 V (0.12%)229.7 V0.47 V (0.2%)11.4 W✓ OK (≤3%)
300 mm²477 A372 A0.23 V (0.1%)229.8 V0.38 V (0.16%)9.1 W✓ OK (≤3%)
400 mm²570 A445 A0.17 V (0.07%)229.8 V0.28 V (0.12%)6.8 W✓ OK (≤3%)

FAQ — Kabelarea för 40 Ampere vid 40 Meter (230V)

Vilken kabelarea krävs för 40A vid 40 meter (230V)?

För 40 Ampere över 40 meter vid 230V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (6.85V / 2.98%).

Hur stor effekt motsvarar 40A vid 230V?

Det motsvarar 9.2 kW med en rekommenderad säkring på 40A.