Kabelarea för 40 Ampere vid 50 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 40 A över 50 m vid 230V.
Copper Cable (≤3% Drop)16 mm²Drop: 5.35V (2.33%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 5.65V (2.46%)
Voltage at Load224.7 VLine Loss: 214.0 W
Max Power & Breaker9.2 kW40A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 50m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 57.07 V (24.81%) | 172.9 V | 94.13 V (40.93%) | 2282.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 34.24 V (14.89%) | 195.8 V | 56.48 V (24.56%) | 1369.6 W | Drop High |
| 4 mm² | 32 A | 25 A | 21.4 V (9.3%) | 208.6 V | 35.3 V (15.35%) | 856.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 14.27 V (6.2%) | 215.7 V | 23.53 V (10.23%) | 570.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 8.56 V (3.72%) | 221.4 V | 14.12 V (6.14%) | 342.4 W | ~ ≤5% |
| 16 mm² | 76 A | 59 A | 5.35 V (2.33%) | 224.7 V | 8.82 V (3.84%) | 214.0 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 3.42 V (1.49%) | 226.6 V | 5.65 V (2.46%) | 137.0 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 2.45 V (1.06%) | 227.6 V | 4.03 V (1.75%) | 97.8 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 1.71 V (0.74%) | 228.3 V | 2.82 V (1.23%) | 68.5 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 1.22 V (0.53%) | 228.8 V | 2.02 V (0.88%) | 48.9 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.9 V (0.39%) | 229.1 V | 1.49 V (0.65%) | 36.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.71 V (0.31%) | 229.3 V | 1.18 V (0.51%) | 28.5 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.57 V (0.25%) | 229.4 V | 0.94 V (0.41%) | 22.8 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.46 V (0.2%) | 229.5 V | 0.76 V (0.33%) | 18.5 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.36 V (0.16%) | 229.6 V | 0.59 V (0.26%) | 14.3 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.29 V (0.12%) | 229.7 V | 0.47 V (0.2%) | 11.4 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.21 V (0.09%) | 229.8 V | 0.35 V (0.15%) | 8.6 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 40 Ampere vid 50 Meter (230V)
Vilken kabelarea krävs för 40A vid 50 meter (230V)?
För 40 Ampere över 50 meter vid 230V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (5.35V / 2.33%).
Hur stor effekt motsvarar 40A vid 230V?
Det motsvarar 9.2 kW med en rekommenderad säkring på 40A.
Related Lengths & Currents (230V)
40A · 5m (230V)40A · 10m (230V)40A · 15m (230V)40A · 20m (230V)40A · 25m (230V)40A · 30m (230V)40A · 35m (230V)40A · 40m (230V)40A · 45m (230V)40A · 60m (230V)40A · 70m (230V)10A · 50m (230V)16A · 50m (230V)20A · 50m (230V)25A · 50m (230V)32A · 50m (230V)50A · 50m (230V)63A · 50m (230V)80A · 50m (230V)100A · 50m (230V)125A · 50m (230V)160A · 50m (230V)200A · 50m (230V)