Kabelarea för 63 Ampere vid 40 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 40 m vid 230V.

Copper Cable (≤3% Drop)16 mm²Drop: 6.74V (2.93%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 5.08V (2.21%)
Voltage at Load223.3 VLine Loss: 424.7 W
Max Power & Breaker14.49 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A71.9 V (31.26%)158.1 V118.61 V (51.57%)4530.0 WDrop High
2.5 mm²24 A18 A43.14 V (18.76%)186.9 V71.16 V (30.94%)2718.0 WDrop High
4 mm²32 A25 A26.96 V (11.72%)203.0 V44.48 V (19.34%)1698.7 WDrop High
6 mm²41 A32 A17.98 V (7.82%)212.0 V29.65 V (12.89%)1132.5 WDrop High
10 mm²57 A44 A10.79 V (4.69%)219.2 V17.79 V (7.74%)679.5 WDrop High
16 mm²76 A59 A6.74 V (2.93%)223.3 V11.12 V (4.83%)424.7 W✓ OK (≤3%)
25 mm²101 A78 A4.31 V (1.88%)225.7 V7.12 V (3.09%)271.8 W✓ OK (≤3%)
35 mm²125 A97 A3.08 V (1.34%)226.9 V5.08 V (2.21%)194.1 W✓ OK (≤3%)
50 mm²151 A118 A2.16 V (0.94%)227.8 V3.56 V (1.55%)135.9 W✓ OK (≤3%)
70 mm²192 A150 A1.54 V (0.67%)228.5 V2.54 V (1.11%)97.1 W✓ OK (≤3%)
95 mm²232 A181 A1.14 V (0.49%)228.9 V1.87 V (0.81%)71.5 W✓ OK (≤3%)
120 mm²269 A210 A0.9 V (0.39%)229.1 V1.48 V (0.64%)56.6 W✓ OK (≤3%)
150 mm²309 A241 A0.72 V (0.31%)229.3 V1.19 V (0.52%)45.3 W✓ OK (≤3%)
185 mm²353 A275 A0.58 V (0.25%)229.4 V0.96 V (0.42%)36.7 W✓ OK (≤3%)
240 mm²415 A324 A0.45 V (0.2%)229.6 V0.74 V (0.32%)28.3 W✓ OK (≤3%)
300 mm²477 A372 A0.36 V (0.16%)229.6 V0.59 V (0.26%)22.6 W✓ OK (≤3%)
400 mm²570 A445 A0.27 V (0.12%)229.7 V0.44 V (0.19%)17.0 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 40 Meter (230V)

Vilken kabelarea krävs för 63A vid 40 meter (230V)?

För 63 Ampere över 40 meter vid 230V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (6.74V / 2.93%).

Hur stor effekt motsvarar 63A vid 230V?

Det motsvarar 14.49 kW med en rekommenderad säkring på 63A.