Kabelarea för 63 Ampere vid 40 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 40 m vid 230V.
Copper Cable (≤3% Drop)16 mm²Drop: 6.74V (2.93%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 5.08V (2.21%)
Voltage at Load223.3 VLine Loss: 424.7 W
Max Power & Breaker14.49 kW63A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 40m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 71.9 V (31.26%) | 158.1 V | 118.61 V (51.57%) | 4530.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 43.14 V (18.76%) | 186.9 V | 71.16 V (30.94%) | 2718.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 26.96 V (11.72%) | 203.0 V | 44.48 V (19.34%) | 1698.7 W | Drop High |
| 6 mm² | 41 A | 32 A | 17.98 V (7.82%) | 212.0 V | 29.65 V (12.89%) | 1132.5 W | Drop High |
| 10 mm² | 57 A | 44 A | 10.79 V (4.69%) | 219.2 V | 17.79 V (7.74%) | 679.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 6.74 V (2.93%) | 223.3 V | 11.12 V (4.83%) | 424.7 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 4.31 V (1.88%) | 225.7 V | 7.12 V (3.09%) | 271.8 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 3.08 V (1.34%) | 226.9 V | 5.08 V (2.21%) | 194.1 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 2.16 V (0.94%) | 227.8 V | 3.56 V (1.55%) | 135.9 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 1.54 V (0.67%) | 228.5 V | 2.54 V (1.11%) | 97.1 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.14 V (0.49%) | 228.9 V | 1.87 V (0.81%) | 71.5 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.9 V (0.39%) | 229.1 V | 1.48 V (0.64%) | 56.6 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.72 V (0.31%) | 229.3 V | 1.19 V (0.52%) | 45.3 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.58 V (0.25%) | 229.4 V | 0.96 V (0.42%) | 36.7 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.45 V (0.2%) | 229.6 V | 0.74 V (0.32%) | 28.3 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.36 V (0.16%) | 229.6 V | 0.59 V (0.26%) | 22.6 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.27 V (0.12%) | 229.7 V | 0.44 V (0.19%) | 17.0 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 63 Ampere vid 40 Meter (230V)
Vilken kabelarea krävs för 63A vid 40 meter (230V)?
För 63 Ampere över 40 meter vid 230V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (6.74V / 2.93%).
Hur stor effekt motsvarar 63A vid 230V?
Det motsvarar 14.49 kW med en rekommenderad säkring på 63A.
Related Lengths & Currents (230V)
63A · 5m (230V)63A · 10m (230V)63A · 15m (230V)63A · 20m (230V)63A · 25m (230V)63A · 30m (230V)63A · 35m (230V)63A · 45m (230V)63A · 50m (230V)63A · 60m (230V)63A · 70m (230V)10A · 40m (230V)16A · 40m (230V)20A · 40m (230V)25A · 40m (230V)32A · 40m (230V)40A · 40m (230V)50A · 40m (230V)80A · 40m (230V)100A · 40m (230V)125A · 40m (230V)160A · 40m (230V)200A · 40m (230V)