Kabelarea för 400 Ampere vid 150 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 400 A över 150 m vid 400V.

Copper Cable (≤3% Drop)240 mm²Drop: 9.27V (2.32%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.17V (2.29%)
Voltage at Load390.7 VLine Loss: 6420.0 W
Max Power & Breaker277.13 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1482.64 V (370.66%)0.0 V2445.66 V (611.41%)1027200.0 WDrop High
2.5 mm²24 A18 A889.58 V (222.4%)0.0 V1467.39 V (366.85%)616320.0 WDrop High
4 mm²32 A25 A555.99 V (139.0%)0.0 V917.12 V (229.28%)385200.0 WDrop High
6 mm²41 A32 A370.66 V (92.66%)29.3 V611.41 V (152.85%)256800.0 WDrop High
10 mm²57 A44 A222.4 V (55.6%)177.6 V366.85 V (91.71%)154080.0 WDrop High
16 mm²76 A59 A139.0 V (34.75%)261.0 V229.28 V (57.32%)96300.0 WDrop High
25 mm²101 A78 A88.96 V (22.24%)311.0 V146.74 V (36.68%)61632.0 WDrop High
35 mm²125 A97 A63.54 V (15.89%)336.5 V104.81 V (26.2%)44022.9 WDrop High
50 mm²151 A118 A44.48 V (11.12%)355.5 V73.37 V (18.34%)30816.0 WDrop High
70 mm²192 A150 A31.77 V (7.94%)368.2 V52.41 V (13.1%)22011.4 WDrop High
95 mm²232 A181 A23.41 V (5.85%)376.6 V38.62 V (9.65%)16218.9 WDrop High
120 mm²269 A210 A18.53 V (4.63%)381.5 V30.57 V (7.64%)12840.0 WDrop High
150 mm²309 A241 A14.83 V (3.71%)385.2 V24.46 V (6.11%)10272.0 WDrop High
185 mm²353 A275 A12.02 V (3.01%)388.0 V19.83 V (4.96%)8328.6 WDrop High
240 mm²415 A324 A9.27 V (2.32%)390.7 V15.29 V (3.82%)6420.0 W✓ OK (≤3%)
300 mm²477 A372 A7.41 V (1.85%)392.6 V12.23 V (3.06%)5136.0 W✓ OK (≤3%)
400 mm²570 A445 A5.56 V (1.39%)394.4 V9.17 V (2.29%)3852.0 W✓ OK (≤3%)

FAQ — Kabelarea för 400 Ampere vid 150 Meter (400V)

Vilken kabelarea krävs för 400A vid 150 meter (400V)?

För 400 Ampere över 150 meter vid 400V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (9.27V / 2.32%).

Hur stor effekt motsvarar 400A vid 400V?

Det motsvarar 277.13 kW med en rekommenderad säkring på 400A.