Kabelarea för 400 Ampere vid 250 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 400 A över 250 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 5.35V (2.33%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 17.65V (7.67%)
Voltage at Load224.7 VLine Loss: 2140.0 W
Max Power & Breaker92.0 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2853.33 V (1240.58%)0.0 V4706.67 V (2046.38%)1141333.3 WDrop High
2.5 mm²24 A18 A1712.0 V (744.35%)0.0 V2824.0 V (1227.83%)684800.0 WDrop High
4 mm²32 A25 A1070.0 V (465.22%)0.0 V1765.0 V (767.39%)428000.0 WDrop High
6 mm²41 A32 A713.33 V (310.14%)0.0 V1176.67 V (511.59%)285333.3 WDrop High
10 mm²57 A44 A428.0 V (186.09%)0.0 V706.0 V (306.96%)171200.0 WDrop High
16 mm²76 A59 A267.5 V (116.3%)0.0 V441.25 V (191.85%)107000.0 WDrop High
25 mm²101 A78 A171.2 V (74.43%)58.8 V282.4 V (122.78%)68480.0 WDrop High
35 mm²125 A97 A122.29 V (53.17%)107.7 V201.71 V (87.7%)48914.3 WDrop High
50 mm²151 A118 A85.6 V (37.22%)144.4 V141.2 V (61.39%)34240.0 WDrop High
70 mm²192 A150 A61.14 V (26.58%)168.9 V100.86 V (43.85%)24457.1 WDrop High
95 mm²232 A181 A45.05 V (19.59%)184.9 V74.32 V (32.31%)18021.1 WDrop High
120 mm²269 A210 A35.67 V (15.51%)194.3 V58.83 V (25.58%)14266.7 WDrop High
150 mm²309 A241 A28.53 V (12.41%)201.5 V47.07 V (20.46%)11413.3 WDrop High
185 mm²353 A275 A23.14 V (10.06%)206.9 V38.16 V (16.59%)9254.1 WDrop High
240 mm²415 A324 A17.83 V (7.75%)212.2 V29.42 V (12.79%)7133.3 WDrop High
300 mm²477 A372 A14.27 V (6.2%)215.7 V23.53 V (10.23%)5706.7 WDrop High
400 mm²570 A445 A10.7 V (4.65%)219.3 V17.65 V (7.67%)4280.0 W~ ≤5%

FAQ — Kabelarea för 400 Ampere vid 250 Meter (230V)

Vilken kabelarea krävs för 400A vid 250 meter (230V)?

För 400 Ampere över 250 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.35V / 2.33%).

Hur stor effekt motsvarar 400A vid 230V?

Det motsvarar 92.0 kW med en rekommenderad säkring på 400A.