Kabelarea för 400 Ampere vid 350 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 400 A över 350 m vid 230V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 4.99V (2.17%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 24.71V (10.74%)
Voltage at Load225.0 VLine Loss: 1997.3 W
Max Power & Breaker92.0 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3994.67 V (1736.81%)0.0 V6589.33 V (2864.93%)1597866.7 WDrop High
2.5 mm²24 A18 A2396.8 V (1042.09%)0.0 V3953.6 V (1718.96%)958720.0 WDrop High
4 mm²32 A25 A1498.0 V (651.3%)0.0 V2471.0 V (1074.35%)599200.0 WDrop High
6 mm²41 A32 A998.67 V (434.2%)0.0 V1647.33 V (716.23%)399466.7 WDrop High
10 mm²57 A44 A599.2 V (260.52%)0.0 V988.4 V (429.74%)239680.0 WDrop High
16 mm²76 A59 A374.5 V (162.83%)0.0 V617.75 V (268.59%)149800.0 WDrop High
25 mm²101 A78 A239.68 V (104.21%)0.0 V395.36 V (171.9%)95872.0 WDrop High
35 mm²125 A97 A171.2 V (74.43%)58.8 V282.4 V (122.78%)68480.0 WDrop High
50 mm²151 A118 A119.84 V (52.1%)110.2 V197.68 V (85.95%)47936.0 WDrop High
70 mm²192 A150 A85.6 V (37.22%)144.4 V141.2 V (61.39%)34240.0 WDrop High
95 mm²232 A181 A63.07 V (27.42%)166.9 V104.04 V (45.24%)25229.5 WDrop High
120 mm²269 A210 A49.93 V (21.71%)180.1 V82.37 V (35.81%)19973.3 WDrop High
150 mm²309 A241 A39.95 V (17.37%)190.1 V65.89 V (28.65%)15978.7 WDrop High
185 mm²353 A275 A32.39 V (14.08%)197.6 V53.43 V (23.23%)12955.7 WDrop High
240 mm²415 A324 A24.97 V (10.86%)205.0 V41.18 V (17.91%)9986.7 WDrop High
300 mm²477 A372 A19.97 V (8.68%)210.0 V32.95 V (14.32%)7989.3 WDrop High
400 mm²570 A445 A14.98 V (6.51%)215.0 V24.71 V (10.74%)5992.0 WDrop High

FAQ — Kabelarea för 400 Ampere vid 350 Meter (230V)

Vilken kabelarea krävs för 400A vid 350 meter (230V)?

För 400 Ampere över 350 meter vid 230V rekommenderas 3× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (4.99V / 2.17%).

Hur stor effekt motsvarar 400A vid 230V?

Det motsvarar 92.0 kW med en rekommenderad säkring på 400A.