Kabelarea för 16 Ampere vid 350 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 16 A över 350 m vid 230V.
Copper Cable (≤3% Drop)35 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 5.65V (2.46%)
Voltage at Load223.2 VLine Loss: 109.6 W
Max Power & Breaker3.68 kW16A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 350m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 159.79 V (69.47%) | 70.2 V | 263.57 V (114.6%) | 2556.6 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 95.87 V (41.68%) | 134.1 V | 158.14 V (68.76%) | 1534.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 59.92 V (26.05%) | 170.1 V | 98.84 V (42.97%) | 958.7 W | Drop High |
| 6 mm² | 41 A | 32 A | 39.95 V (17.37%) | 190.1 V | 65.89 V (28.65%) | 639.1 W | Drop High |
| 10 mm² | 57 A | 44 A | 23.97 V (10.42%) | 206.0 V | 39.54 V (17.19%) | 383.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 14.98 V (6.51%) | 215.0 V | 24.71 V (10.74%) | 239.7 W | Drop High |
| 25 mm² | 101 A | 78 A | 9.59 V (4.17%) | 220.4 V | 15.81 V (6.88%) | 153.4 W | ~ ≤5% |
| 35 mm² | 125 A | 97 A | 6.85 V (2.98%) | 223.2 V | 11.3 V (4.91%) | 109.6 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 4.79 V (2.08%) | 225.2 V | 7.91 V (3.44%) | 76.7 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 3.42 V (1.49%) | 226.6 V | 5.65 V (2.46%) | 54.8 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 2.52 V (1.1%) | 227.5 V | 4.16 V (1.81%) | 40.4 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 2.0 V (0.87%) | 228.0 V | 3.29 V (1.43%) | 32.0 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.6 V (0.69%) | 228.4 V | 2.64 V (1.15%) | 25.6 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 1.3 V (0.56%) | 228.7 V | 2.14 V (0.93%) | 20.7 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 1.0 V (0.43%) | 229.0 V | 1.65 V (0.72%) | 16.0 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.8 V (0.35%) | 229.2 V | 1.32 V (0.57%) | 12.8 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.6 V (0.26%) | 229.4 V | 0.99 V (0.43%) | 9.6 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 16 Ampere vid 350 Meter (230V)
Vilken kabelarea krävs för 16A vid 350 meter (230V)?
För 16 Ampere över 350 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (6.85V / 2.98%).
Hur stor effekt motsvarar 16A vid 230V?
Det motsvarar 3.68 kW med en rekommenderad säkring på 16A.
Related Lengths & Currents (230V)
16A · 5m (230V)16A · 10m (230V)16A · 15m (230V)16A · 20m (230V)16A · 25m (230V)16A · 30m (230V)16A · 35m (230V)16A · 40m (230V)16A · 45m (230V)16A · 50m (230V)16A · 60m (230V)16A · 70m (230V)10A · 350m (230V)20A · 350m (230V)25A · 350m (230V)32A · 350m (230V)40A · 350m (230V)50A · 350m (230V)63A · 350m (230V)80A · 350m (230V)100A · 350m (230V)125A · 350m (230V)160A · 350m (230V)200A · 350m (230V)