Kabelarea för 160 Ampere vid 350 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 160 A över 350 m vid 230V.
Copper Cable (≤3% Drop)400 mm²Drop: 5.99V (2.61%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.88V (4.3%)
Voltage at Load224.0 VLine Loss: 958.7 W
Max Power & Breaker36.8 kW160A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 350m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1597.87 V (694.72%) | 0.0 V | 2635.73 V (1145.97%) | 255658.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 958.72 V (416.83%) | 0.0 V | 1581.44 V (687.58%) | 153395.2 W | Drop High |
| 4 mm² | 32 A | 25 A | 599.2 V (260.52%) | 0.0 V | 988.4 V (429.74%) | 95872.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 399.47 V (173.68%) | 0.0 V | 658.93 V (286.49%) | 63914.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 239.68 V (104.21%) | 0.0 V | 395.36 V (171.9%) | 38348.8 W | Drop High |
| 16 mm² | 76 A | 59 A | 149.8 V (65.13%) | 80.2 V | 247.1 V (107.43%) | 23968.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 95.87 V (41.68%) | 134.1 V | 158.14 V (68.76%) | 15339.5 W | Drop High |
| 35 mm² | 125 A | 97 A | 68.48 V (29.77%) | 161.5 V | 112.96 V (49.11%) | 10956.8 W | Drop High |
| 50 mm² | 151 A | 118 A | 47.94 V (20.84%) | 182.1 V | 79.07 V (34.38%) | 7669.8 W | Drop High |
| 70 mm² | 192 A | 150 A | 34.24 V (14.89%) | 195.8 V | 56.48 V (24.56%) | 5478.4 W | Drop High |
| 95 mm² | 232 A | 181 A | 25.23 V (10.97%) | 204.8 V | 41.62 V (18.09%) | 4036.7 W | Drop High |
| 120 mm² | 269 A | 210 A | 19.97 V (8.68%) | 210.0 V | 32.95 V (14.32%) | 3195.7 W | Drop High |
| 150 mm² | 309 A | 241 A | 15.98 V (6.95%) | 214.0 V | 26.36 V (11.46%) | 2556.6 W | Drop High |
| 185 mm² | 353 A | 275 A | 12.96 V (5.63%) | 217.0 V | 21.37 V (9.29%) | 2072.9 W | Drop High |
| 240 mm² | 415 A | 324 A | 9.99 V (4.34%) | 220.0 V | 16.47 V (7.16%) | 1597.9 W | ~ ≤5% |
| 300 mm² | 477 A | 372 A | 7.99 V (3.47%) | 222.0 V | 13.18 V (5.73%) | 1278.3 W | ~ ≤5% |
| 400 mm² | 570 A | 445 A | 5.99 V (2.61%) | 224.0 V | 9.88 V (4.3%) | 958.7 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 160 Ampere vid 350 Meter (230V)
Vilken kabelarea krävs för 160A vid 350 meter (230V)?
För 160 Ampere över 350 meter vid 230V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.99V / 2.61%).
Hur stor effekt motsvarar 160A vid 230V?
Det motsvarar 36.8 kW med en rekommenderad säkring på 160A.
Related Lengths & Currents (230V)
160A · 5m (230V)160A · 10m (230V)160A · 15m (230V)160A · 20m (230V)160A · 25m (230V)160A · 30m (230V)160A · 35m (230V)160A · 40m (230V)160A · 45m (230V)160A · 50m (230V)160A · 60m (230V)160A · 70m (230V)10A · 350m (230V)16A · 350m (230V)20A · 350m (230V)25A · 350m (230V)32A · 350m (230V)40A · 350m (230V)50A · 350m (230V)63A · 350m (230V)80A · 350m (230V)100A · 350m (230V)125A · 350m (230V)200A · 350m (230V)