Kabelarea för 160 Ampere vid 350 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 160 A över 350 m vid 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 5.99V (2.61%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.88V (4.3%)
Voltage at Load224.0 VLine Loss: 958.7 W
Max Power & Breaker36.8 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1597.87 V (694.72%)0.0 V2635.73 V (1145.97%)255658.7 WDrop High
2.5 mm²24 A18 A958.72 V (416.83%)0.0 V1581.44 V (687.58%)153395.2 WDrop High
4 mm²32 A25 A599.2 V (260.52%)0.0 V988.4 V (429.74%)95872.0 WDrop High
6 mm²41 A32 A399.47 V (173.68%)0.0 V658.93 V (286.49%)63914.7 WDrop High
10 mm²57 A44 A239.68 V (104.21%)0.0 V395.36 V (171.9%)38348.8 WDrop High
16 mm²76 A59 A149.8 V (65.13%)80.2 V247.1 V (107.43%)23968.0 WDrop High
25 mm²101 A78 A95.87 V (41.68%)134.1 V158.14 V (68.76%)15339.5 WDrop High
35 mm²125 A97 A68.48 V (29.77%)161.5 V112.96 V (49.11%)10956.8 WDrop High
50 mm²151 A118 A47.94 V (20.84%)182.1 V79.07 V (34.38%)7669.8 WDrop High
70 mm²192 A150 A34.24 V (14.89%)195.8 V56.48 V (24.56%)5478.4 WDrop High
95 mm²232 A181 A25.23 V (10.97%)204.8 V41.62 V (18.09%)4036.7 WDrop High
120 mm²269 A210 A19.97 V (8.68%)210.0 V32.95 V (14.32%)3195.7 WDrop High
150 mm²309 A241 A15.98 V (6.95%)214.0 V26.36 V (11.46%)2556.6 WDrop High
185 mm²353 A275 A12.96 V (5.63%)217.0 V21.37 V (9.29%)2072.9 WDrop High
240 mm²415 A324 A9.99 V (4.34%)220.0 V16.47 V (7.16%)1597.9 W~ ≤5%
300 mm²477 A372 A7.99 V (3.47%)222.0 V13.18 V (5.73%)1278.3 W~ ≤5%
400 mm²570 A445 A5.99 V (2.61%)224.0 V9.88 V (4.3%)958.7 W✓ OK (≤3%)

FAQ — Kabelarea för 160 Ampere vid 350 Meter (230V)

Vilken kabelarea krävs för 160A vid 350 meter (230V)?

För 160 Ampere över 350 meter vid 230V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.99V / 2.61%).

Hur stor effekt motsvarar 160A vid 230V?

Det motsvarar 36.8 kW med en rekommenderad säkring på 160A.