Kabelarea för 63 Ampere vid 350 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 350 m vid 230V.

Copper Cable (≤3% Drop)150 mm²Drop: 6.29V (2.74%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 6.49V (2.82%)
Voltage at Load223.7 VLine Loss: 396.4 W
Max Power & Breaker14.49 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A629.16 V (273.55%)0.0 V1037.82 V (451.23%)39637.1 WDrop High
2.5 mm²24 A18 A377.5 V (164.13%)0.0 V622.69 V (270.74%)23782.2 WDrop High
4 mm²32 A25 A235.93 V (102.58%)0.0 V389.18 V (169.21%)14863.9 WDrop High
6 mm²41 A32 A157.29 V (68.39%)72.7 V259.45 V (112.81%)9909.3 WDrop High
10 mm²57 A44 A94.37 V (41.03%)135.6 V155.67 V (67.68%)5945.6 WDrop High
16 mm²76 A59 A58.98 V (25.65%)171.0 V97.3 V (42.3%)3716.0 WDrop High
25 mm²101 A78 A37.75 V (16.41%)192.3 V62.27 V (27.07%)2378.2 WDrop High
35 mm²125 A97 A26.96 V (11.72%)203.0 V44.48 V (19.34%)1698.7 WDrop High
50 mm²151 A118 A18.87 V (8.21%)211.1 V31.13 V (13.54%)1189.1 WDrop High
70 mm²192 A150 A13.48 V (5.86%)216.5 V22.24 V (9.67%)849.4 WDrop High
95 mm²232 A181 A9.93 V (4.32%)220.1 V16.39 V (7.12%)625.8 W~ ≤5%
120 mm²269 A210 A7.86 V (3.42%)222.1 V12.97 V (5.64%)495.5 W~ ≤5%
150 mm²309 A241 A6.29 V (2.74%)223.7 V10.38 V (4.51%)396.4 W✓ OK (≤3%)
185 mm²353 A275 A5.1 V (2.22%)224.9 V8.41 V (3.66%)321.4 W✓ OK (≤3%)
240 mm²415 A324 A3.93 V (1.71%)226.1 V6.49 V (2.82%)247.7 W✓ OK (≤3%)
300 mm²477 A372 A3.15 V (1.37%)226.9 V5.19 V (2.26%)198.2 W✓ OK (≤3%)
400 mm²570 A445 A2.36 V (1.03%)227.6 V3.89 V (1.69%)148.6 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 350 Meter (230V)

Vilken kabelarea krävs för 63A vid 350 meter (230V)?

För 63 Ampere över 350 meter vid 230V rekommenderas 150 mm² kopparkabel för att hålla spänningsfallet under 3% (6.29V / 2.74%).

Hur stor effekt motsvarar 63A vid 230V?

Det motsvarar 14.49 kW med en rekommenderad säkring på 63A.