Kabelarea för 450 Ampere vid 500 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 450 A över 500 m vid 230V.

Copper Cable (≤3% Drop)4× 400 mm²Drop: 6.02V (2.62%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 39.71V (17.27%)
Voltage at Load224.0 VLine Loss: 2708.4 W
Max Power & Breaker103.5 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6420.0 V (2791.3%)0.0 V10590.0 V (4604.35%)2889000.0 WDrop High
2.5 mm²24 A18 A3852.0 V (1674.78%)0.0 V6354.0 V (2762.61%)1733400.0 WDrop High
4 mm²32 A25 A2407.5 V (1046.74%)0.0 V3971.25 V (1726.63%)1083375.0 WDrop High
6 mm²41 A32 A1605.0 V (697.83%)0.0 V2647.5 V (1151.09%)722250.0 WDrop High
10 mm²57 A44 A963.0 V (418.7%)0.0 V1588.5 V (690.65%)433350.0 WDrop High
16 mm²76 A59 A601.88 V (261.68%)0.0 V992.81 V (431.66%)270843.8 WDrop High
25 mm²101 A78 A385.2 V (167.48%)0.0 V635.4 V (276.26%)173340.0 WDrop High
35 mm²125 A97 A275.14 V (119.63%)0.0 V453.86 V (197.33%)123814.3 WDrop High
50 mm²151 A118 A192.6 V (83.74%)37.4 V317.7 V (138.13%)86670.0 WDrop High
70 mm²192 A150 A137.57 V (59.81%)92.4 V226.93 V (98.66%)61907.1 WDrop High
95 mm²232 A181 A101.37 V (44.07%)128.6 V167.21 V (72.7%)45615.8 WDrop High
120 mm²269 A210 A80.25 V (34.89%)149.8 V132.37 V (57.55%)36112.5 WDrop High
150 mm²309 A241 A64.2 V (27.91%)165.8 V105.9 V (46.04%)28890.0 WDrop High
185 mm²353 A275 A52.05 V (22.63%)177.9 V85.86 V (37.33%)23424.3 WDrop High
240 mm²415 A324 A40.12 V (17.45%)189.9 V66.19 V (28.78%)18056.2 WDrop High
300 mm²477 A372 A32.1 V (13.96%)197.9 V52.95 V (23.02%)14445.0 WDrop High
400 mm²570 A445 A24.07 V (10.47%)205.9 V39.71 V (17.27%)10833.8 WDrop High

FAQ — Kabelarea för 450 Ampere vid 500 Meter (230V)

Vilken kabelarea krävs för 450A vid 500 meter (230V)?

För 450 Ampere över 500 meter vid 230V rekommenderas 4× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.02V / 2.62%).

Hur stor effekt motsvarar 450A vid 230V?

Det motsvarar 103.5 kW med en rekommenderad säkring på 450A.