Kabelarea för 5 Ampere vid 175 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 5 A över 175 m vid 230V.

Copper Cable (≤3% Drop)6 mm²Drop: 6.24V (2.71%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 6.18V (2.69%)
Voltage at Load223.8 VLine Loss: 31.2 W
Max Power & Breaker1.15 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A24.97 V (10.86%)205.0 V41.18 V (17.91%)124.8 WDrop High
2.5 mm²24 A18 A14.98 V (6.51%)215.0 V24.71 V (10.74%)74.9 WDrop High
4 mm²32 A25 A9.36 V (4.07%)220.6 V15.44 V (6.71%)46.8 W~ ≤5%
6 mm²41 A32 A6.24 V (2.71%)223.8 V10.3 V (4.48%)31.2 W✓ OK (≤3%)
10 mm²57 A44 A3.74 V (1.63%)226.3 V6.18 V (2.69%)18.7 W✓ OK (≤3%)
16 mm²76 A59 A2.34 V (1.02%)227.7 V3.86 V (1.68%)11.7 W✓ OK (≤3%)
25 mm²101 A78 A1.5 V (0.65%)228.5 V2.47 V (1.07%)7.5 W✓ OK (≤3%)
35 mm²125 A97 A1.07 V (0.47%)228.9 V1.76 V (0.77%)5.3 W✓ OK (≤3%)
50 mm²151 A118 A0.75 V (0.33%)229.3 V1.24 V (0.54%)3.7 W✓ OK (≤3%)
70 mm²192 A150 A0.53 V (0.23%)229.5 V0.88 V (0.38%)2.7 W✓ OK (≤3%)
95 mm²232 A181 A0.39 V (0.17%)229.6 V0.65 V (0.28%)2.0 W✓ OK (≤3%)
120 mm²269 A210 A0.31 V (0.14%)229.7 V0.51 V (0.22%)1.6 W✓ OK (≤3%)
150 mm²309 A241 A0.25 V (0.11%)229.8 V0.41 V (0.18%)1.2 W✓ OK (≤3%)
185 mm²353 A275 A0.2 V (0.09%)229.8 V0.33 V (0.15%)1.0 W✓ OK (≤3%)
240 mm²415 A324 A0.16 V (0.07%)229.8 V0.26 V (0.11%)0.8 W✓ OK (≤3%)
300 mm²477 A372 A0.12 V (0.05%)229.9 V0.21 V (0.09%)0.6 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.04%)229.9 V0.15 V (0.07%)0.5 W✓ OK (≤3%)

FAQ — Kabelarea för 5 Ampere vid 175 Meter (230V)

Vilken kabelarea krävs för 5A vid 175 meter (230V)?

För 5 Ampere över 175 meter vid 230V rekommenderas 6 mm² kopparkabel för att hålla spänningsfallet under 3% (6.24V / 2.71%).

Hur stor effekt motsvarar 5A vid 230V?

Det motsvarar 1.15 kW med en rekommenderad säkring på 6A.