Kabelarea för 50 Ampere vid 175 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 50 A över 175 m vid 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 9.27V (2.32%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 10.7V (2.67%)
Voltage at Load390.7 VLine Loss: 802.5 W
Max Power & Breaker34.64 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A216.22 V (54.05%)183.8 V356.66 V (89.16%)18725.0 WDrop High
2.5 mm²24 A18 A129.73 V (32.43%)270.3 V213.99 V (53.5%)11235.0 WDrop High
4 mm²32 A25 A81.08 V (20.27%)318.9 V133.75 V (33.44%)7021.9 WDrop High
6 mm²41 A32 A54.05 V (13.51%)345.9 V89.16 V (22.29%)4681.2 WDrop High
10 mm²57 A44 A32.43 V (8.11%)367.6 V53.5 V (13.37%)2808.7 WDrop High
16 mm²76 A59 A20.27 V (5.07%)379.7 V33.44 V (8.36%)1755.5 WDrop High
25 mm²101 A78 A12.97 V (3.24%)387.0 V21.4 V (5.35%)1123.5 W~ ≤5%
35 mm²125 A97 A9.27 V (2.32%)390.7 V15.29 V (3.82%)802.5 W✓ OK (≤3%)
50 mm²151 A118 A6.49 V (1.62%)393.5 V10.7 V (2.67%)561.8 W✓ OK (≤3%)
70 mm²192 A150 A4.63 V (1.16%)395.4 V7.64 V (1.91%)401.2 W✓ OK (≤3%)
95 mm²232 A181 A3.41 V (0.85%)396.6 V5.63 V (1.41%)295.7 W✓ OK (≤3%)
120 mm²269 A210 A2.7 V (0.68%)397.3 V4.46 V (1.11%)234.1 W✓ OK (≤3%)
150 mm²309 A241 A2.16 V (0.54%)397.8 V3.57 V (0.89%)187.2 W✓ OK (≤3%)
185 mm²353 A275 A1.75 V (0.44%)398.2 V2.89 V (0.72%)151.8 W✓ OK (≤3%)
240 mm²415 A324 A1.35 V (0.34%)398.6 V2.23 V (0.56%)117.0 W✓ OK (≤3%)
300 mm²477 A372 A1.08 V (0.27%)398.9 V1.78 V (0.45%)93.6 W✓ OK (≤3%)
400 mm²570 A445 A0.81 V (0.2%)399.2 V1.34 V (0.33%)70.2 W✓ OK (≤3%)

FAQ — Kabelarea för 50 Ampere vid 175 Meter (400V)

Vilken kabelarea krävs för 50A vid 175 meter (400V)?

För 50 Ampere över 175 meter vid 400V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (9.27V / 2.32%).

Hur stor effekt motsvarar 50A vid 400V?

Det motsvarar 34.64 kW med en rekommenderad säkring på 50A.