Kabelarea för 50 Ampere vid 175 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 50 A över 175 m vid 400V.
Copper Cable (≤3% Drop)35 mm²Drop: 9.27V (2.32%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 10.7V (2.67%)
Voltage at Load390.7 VLine Loss: 802.5 W
Max Power & Breaker34.64 kW50A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 175m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 216.22 V (54.05%) | 183.8 V | 356.66 V (89.16%) | 18725.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 129.73 V (32.43%) | 270.3 V | 213.99 V (53.5%) | 11235.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 81.08 V (20.27%) | 318.9 V | 133.75 V (33.44%) | 7021.9 W | Drop High |
| 6 mm² | 41 A | 32 A | 54.05 V (13.51%) | 345.9 V | 89.16 V (22.29%) | 4681.2 W | Drop High |
| 10 mm² | 57 A | 44 A | 32.43 V (8.11%) | 367.6 V | 53.5 V (13.37%) | 2808.7 W | Drop High |
| 16 mm² | 76 A | 59 A | 20.27 V (5.07%) | 379.7 V | 33.44 V (8.36%) | 1755.5 W | Drop High |
| 25 mm² | 101 A | 78 A | 12.97 V (3.24%) | 387.0 V | 21.4 V (5.35%) | 1123.5 W | ~ ≤5% |
| 35 mm² | 125 A | 97 A | 9.27 V (2.32%) | 390.7 V | 15.29 V (3.82%) | 802.5 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 6.49 V (1.62%) | 393.5 V | 10.7 V (2.67%) | 561.8 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 4.63 V (1.16%) | 395.4 V | 7.64 V (1.91%) | 401.2 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 3.41 V (0.85%) | 396.6 V | 5.63 V (1.41%) | 295.7 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 2.7 V (0.68%) | 397.3 V | 4.46 V (1.11%) | 234.1 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 2.16 V (0.54%) | 397.8 V | 3.57 V (0.89%) | 187.2 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 1.75 V (0.44%) | 398.2 V | 2.89 V (0.72%) | 151.8 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 1.35 V (0.34%) | 398.6 V | 2.23 V (0.56%) | 117.0 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 1.08 V (0.27%) | 398.9 V | 1.78 V (0.45%) | 93.6 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.81 V (0.2%) | 399.2 V | 1.34 V (0.33%) | 70.2 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 50 Ampere vid 175 Meter (400V)
Vilken kabelarea krävs för 50A vid 175 meter (400V)?
För 50 Ampere över 175 meter vid 400V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (9.27V / 2.32%).
Hur stor effekt motsvarar 50A vid 400V?
Det motsvarar 34.64 kW med en rekommenderad säkring på 50A.
Related Lengths & Currents (400V)
50A · 5m (400V)50A · 10m (400V)50A · 15m (400V)50A · 20m (400V)50A · 25m (400V)50A · 30m (400V)50A · 35m (400V)50A · 40m (400V)50A · 45m (400V)50A · 50m (400V)50A · 60m (400V)50A · 70m (400V)10A · 175m (400V)16A · 175m (400V)20A · 175m (400V)25A · 175m (400V)32A · 175m (400V)40A · 175m (400V)63A · 175m (400V)80A · 175m (400V)100A · 175m (400V)125A · 175m (400V)160A · 175m (400V)200A · 175m (400V)