Kabelarea för 100 Ampere vid 175 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 100 A över 175 m vid 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 9.27V (2.32%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 11.26V (2.82%)
Voltage at Load390.7 VLine Loss: 1605.0 W
Max Power & Breaker69.28 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A432.44 V (108.11%)0.0 V713.32 V (178.33%)74900.0 WDrop High
2.5 mm²24 A18 A259.46 V (64.87%)140.5 V427.99 V (107.0%)44940.0 WDrop High
4 mm²32 A25 A162.16 V (40.54%)237.8 V267.49 V (66.87%)28087.5 WDrop High
6 mm²41 A32 A108.11 V (27.03%)291.9 V178.33 V (44.58%)18725.0 WDrop High
10 mm²57 A44 A64.87 V (16.22%)335.1 V107.0 V (26.75%)11235.0 WDrop High
16 mm²76 A59 A40.54 V (10.14%)359.5 V66.87 V (16.72%)7021.9 WDrop High
25 mm²101 A78 A25.95 V (6.49%)374.1 V42.8 V (10.7%)4494.0 WDrop High
35 mm²125 A97 A18.53 V (4.63%)381.5 V30.57 V (7.64%)3210.0 W~ ≤5%
50 mm²151 A118 A12.97 V (3.24%)387.0 V21.4 V (5.35%)2247.0 W~ ≤5%
70 mm²192 A150 A9.27 V (2.32%)390.7 V15.29 V (3.82%)1605.0 W✓ OK (≤3%)
95 mm²232 A181 A6.83 V (1.71%)393.2 V11.26 V (2.82%)1182.6 W✓ OK (≤3%)
120 mm²269 A210 A5.41 V (1.35%)394.6 V8.92 V (2.23%)936.2 W✓ OK (≤3%)
150 mm²309 A241 A4.32 V (1.08%)395.7 V7.13 V (1.78%)749.0 W✓ OK (≤3%)
185 mm²353 A275 A3.51 V (0.88%)396.5 V5.78 V (1.45%)607.3 W✓ OK (≤3%)
240 mm²415 A324 A2.7 V (0.68%)397.3 V4.46 V (1.11%)468.1 W✓ OK (≤3%)
300 mm²477 A372 A2.16 V (0.54%)397.8 V3.57 V (0.89%)374.5 W✓ OK (≤3%)
400 mm²570 A445 A1.62 V (0.41%)398.4 V2.67 V (0.67%)280.9 W✓ OK (≤3%)

FAQ — Kabelarea för 100 Ampere vid 175 Meter (400V)

Vilken kabelarea krävs för 100A vid 175 meter (400V)?

För 100 Ampere över 175 meter vid 400V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (9.27V / 2.32%).

Hur stor effekt motsvarar 100A vid 400V?

Det motsvarar 69.28 kW med en rekommenderad säkring på 100A.