Kabelarea för 125 Ampere vid 175 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 125 A över 175 m vid 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 11.58V (2.9%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 11.15V (2.79%)
Voltage at Load388.4 VLine Loss: 2507.8 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A540.54 V (135.14%)0.0 V891.65 V (222.91%)117031.2 WDrop High
2.5 mm²24 A18 A324.33 V (81.08%)75.7 V534.99 V (133.75%)70218.7 WDrop High
4 mm²32 A25 A202.7 V (50.68%)197.3 V334.37 V (83.59%)43886.7 WDrop High
6 mm²41 A32 A135.14 V (33.78%)264.9 V222.91 V (55.73%)29257.8 WDrop High
10 mm²57 A44 A81.08 V (20.27%)318.9 V133.75 V (33.44%)17554.7 WDrop High
16 mm²76 A59 A50.68 V (12.67%)349.3 V83.59 V (20.9%)10971.7 WDrop High
25 mm²101 A78 A32.43 V (8.11%)367.6 V53.5 V (13.37%)7021.9 WDrop High
35 mm²125 A97 A23.17 V (5.79%)376.8 V38.21 V (9.55%)5015.6 WDrop High
50 mm²151 A118 A16.22 V (4.05%)383.8 V26.75 V (6.69%)3510.9 W~ ≤5%
70 mm²192 A150 A11.58 V (2.9%)388.4 V19.11 V (4.78%)2507.8 W✓ OK (≤3%)
95 mm²232 A181 A8.53 V (2.13%)391.5 V14.08 V (3.52%)1847.9 W✓ OK (≤3%)
120 mm²269 A210 A6.76 V (1.69%)393.2 V11.15 V (2.79%)1462.9 W✓ OK (≤3%)
150 mm²309 A241 A5.41 V (1.35%)394.6 V8.92 V (2.23%)1170.3 W✓ OK (≤3%)
185 mm²353 A275 A4.38 V (1.1%)395.6 V7.23 V (1.81%)948.9 W✓ OK (≤3%)
240 mm²415 A324 A3.38 V (0.84%)396.6 V5.57 V (1.39%)731.4 W✓ OK (≤3%)
300 mm²477 A372 A2.7 V (0.68%)397.3 V4.46 V (1.11%)585.2 W✓ OK (≤3%)
400 mm²570 A445 A2.03 V (0.51%)398.0 V3.34 V (0.84%)438.9 W✓ OK (≤3%)

FAQ — Kabelarea för 125 Ampere vid 175 Meter (400V)

Vilken kabelarea krävs för 125A vid 175 meter (400V)?

För 125 Ampere över 175 meter vid 400V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (11.58V / 2.9%).

Hur stor effekt motsvarar 125A vid 400V?

Det motsvarar 86.6 kW med en rekommenderad säkring på 125A.