⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 32 Ampere vid 175 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 175 m vid 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 8.3V (2.08%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 9.78V (2.45%)
Voltage at Load391.7 VLine Loss: 460.2 W
Max Power & Breaker22.17 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A138.38 V (34.59%)261.6 V228.26 V (57.07%)7669.8 WDrop High
2.5 mm²24 A18 A83.03 V (20.76%)317.0 V136.96 V (34.24%)4601.9 WDrop High
4 mm²32 A25 A51.89 V (12.97%)348.1 V85.6 V (21.4%)2876.2 WDrop High
6 mm²41 A32 A34.59 V (8.65%)365.4 V57.07 V (14.27%)1917.4 WDrop High
10 mm²57 A44 A20.76 V (5.19%)379.2 V34.24 V (8.56%)1150.5 WDrop High
16 mm²76 A59 A12.97 V (3.24%)387.0 V21.4 V (5.35%)719.0 W~ ≤5%
25 mm²101 A78 A8.3 V (2.08%)391.7 V13.7 V (3.42%)460.2 W✓ OK (≤3%)
35 mm²125 A97 A5.93 V (1.48%)394.1 V9.78 V (2.45%)328.7 W✓ OK (≤3%)
50 mm²151 A118 A4.15 V (1.04%)395.8 V6.85 V (1.71%)230.1 W✓ OK (≤3%)
70 mm²192 A150 A2.97 V (0.74%)397.0 V4.89 V (1.22%)164.4 W✓ OK (≤3%)
95 mm²232 A181 A2.18 V (0.55%)397.8 V3.6 V (0.9%)121.1 W✓ OK (≤3%)
120 mm²269 A210 A1.73 V (0.43%)398.3 V2.85 V (0.71%)95.9 W✓ OK (≤3%)
150 mm²309 A241 A1.38 V (0.35%)398.6 V2.28 V (0.57%)76.7 W✓ OK (≤3%)
185 mm²353 A275 A1.12 V (0.28%)398.9 V1.85 V (0.46%)62.2 W✓ OK (≤3%)
240 mm²415 A324 A0.86 V (0.22%)399.1 V1.43 V (0.36%)47.9 W✓ OK (≤3%)
300 mm²477 A372 A0.69 V (0.17%)399.3 V1.14 V (0.29%)38.3 W✓ OK (≤3%)
400 mm²570 A445 A0.52 V (0.13%)399.5 V0.86 V (0.21%)28.8 W✓ OK (≤3%)

FAQ — Kabelarea för 32 Ampere vid 175 Meter (400V)

Vilken kabelarea krävs för 32A vid 175 meter (400V)?

För 32 Ampere över 175 meter vid 400V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (8.3V / 2.08%).

Hur stor effekt motsvarar 32A vid 400V?

Det motsvarar 22.17 kW med en rekommenderad säkring på 32A.