Kabelarea för 100 Ampere vid 50 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 100 A över 50 m vid 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 6.11V (2.66%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 5.04V (2.19%)
Voltage at Load223.9 VLine Loss: 611.4 W
Max Power & Breaker23.0 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A142.67 V (62.03%)87.3 V235.33 V (102.32%)14266.7 WDrop High
2.5 mm²24 A18 A85.6 V (37.22%)144.4 V141.2 V (61.39%)8560.0 WDrop High
4 mm²32 A25 A53.5 V (23.26%)176.5 V88.25 V (38.37%)5350.0 WDrop High
6 mm²41 A32 A35.67 V (15.51%)194.3 V58.83 V (25.58%)3566.7 WDrop High
10 mm²57 A44 A21.4 V (9.3%)208.6 V35.3 V (15.35%)2140.0 WDrop High
16 mm²76 A59 A13.37 V (5.82%)216.6 V22.06 V (9.59%)1337.5 WDrop High
25 mm²101 A78 A8.56 V (3.72%)221.4 V14.12 V (6.14%)856.0 W~ ≤5%
35 mm²125 A97 A6.11 V (2.66%)223.9 V10.09 V (4.39%)611.4 W✓ OK (≤3%)
50 mm²151 A118 A4.28 V (1.86%)225.7 V7.06 V (3.07%)428.0 W✓ OK (≤3%)
70 mm²192 A150 A3.06 V (1.33%)226.9 V5.04 V (2.19%)305.7 W✓ OK (≤3%)
95 mm²232 A181 A2.25 V (0.98%)227.7 V3.72 V (1.62%)225.3 W✓ OK (≤3%)
120 mm²269 A210 A1.78 V (0.78%)228.2 V2.94 V (1.28%)178.3 W✓ OK (≤3%)
150 mm²309 A241 A1.43 V (0.62%)228.6 V2.35 V (1.02%)142.7 W✓ OK (≤3%)
185 mm²353 A275 A1.16 V (0.5%)228.8 V1.91 V (0.83%)115.7 W✓ OK (≤3%)
240 mm²415 A324 A0.89 V (0.39%)229.1 V1.47 V (0.64%)89.2 W✓ OK (≤3%)
300 mm²477 A372 A0.71 V (0.31%)229.3 V1.18 V (0.51%)71.3 W✓ OK (≤3%)
400 mm²570 A445 A0.53 V (0.23%)229.5 V0.88 V (0.38%)53.5 W✓ OK (≤3%)

FAQ — Kabelarea för 100 Ampere vid 50 Meter (230V)

Vilken kabelarea krävs för 100A vid 50 meter (230V)?

För 100 Ampere över 50 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (6.11V / 2.66%).

Hur stor effekt motsvarar 100A vid 230V?

Det motsvarar 23.0 kW med en rekommenderad säkring på 100A.