Kabelarea för 500 Ampere vid 250 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 500 A över 250 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.69V (2.91%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 22.06V (9.59%)
Voltage at Load223.3 VLine Loss: 3343.8 W
Max Power & Breaker115.0 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3566.67 V (1550.72%)0.0 V5883.33 V (2557.97%)1783333.3 WDrop High
2.5 mm²24 A18 A2140.0 V (930.43%)0.0 V3530.0 V (1534.78%)1070000.0 WDrop High
4 mm²32 A25 A1337.5 V (581.52%)0.0 V2206.25 V (959.24%)668750.0 WDrop High
6 mm²41 A32 A891.67 V (387.68%)0.0 V1470.83 V (639.49%)445833.3 WDrop High
10 mm²57 A44 A535.0 V (232.61%)0.0 V882.5 V (383.7%)267500.0 WDrop High
16 mm²76 A59 A334.38 V (145.38%)0.0 V551.56 V (239.81%)167187.5 WDrop High
25 mm²101 A78 A214.0 V (93.04%)16.0 V353.0 V (153.48%)107000.0 WDrop High
35 mm²125 A97 A152.86 V (66.46%)77.1 V252.14 V (109.63%)76428.6 WDrop High
50 mm²151 A118 A107.0 V (46.52%)123.0 V176.5 V (76.74%)53500.0 WDrop High
70 mm²192 A150 A76.43 V (33.23%)153.6 V126.07 V (54.81%)38214.3 WDrop High
95 mm²232 A181 A56.32 V (24.49%)173.7 V92.89 V (40.39%)28157.9 WDrop High
120 mm²269 A210 A44.58 V (19.38%)185.4 V73.54 V (31.97%)22291.7 WDrop High
150 mm²309 A241 A35.67 V (15.51%)194.3 V58.83 V (25.58%)17833.3 WDrop High
185 mm²353 A275 A28.92 V (12.57%)201.1 V47.7 V (20.74%)14459.5 WDrop High
240 mm²415 A324 A22.29 V (9.69%)207.7 V36.77 V (15.99%)11145.8 WDrop High
300 mm²477 A372 A17.83 V (7.75%)212.2 V29.42 V (12.79%)8916.7 WDrop High
400 mm²570 A445 A13.38 V (5.82%)216.6 V22.06 V (9.59%)6687.5 WDrop High

FAQ — Kabelarea för 500 Ampere vid 250 Meter (230V)

Vilken kabelarea krävs för 500A vid 250 meter (230V)?

För 500 Ampere över 250 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.69V / 2.91%).

Hur stor effekt motsvarar 500A vid 230V?

Det motsvarar 115.0 kW med en rekommenderad säkring på 500A.