Kabelarea för 550 Ampere vid 70 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 550 A över 70 m vid 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 3.57V (0.89%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.88V (1.47%)
Voltage at Load396.4 VLine Loss: 3398.6 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A951.36 V (237.84%)0.0 V1569.3 V (392.32%)906290.0 WDrop High
2.5 mm²24 A18 A570.81 V (142.7%)0.0 V941.58 V (235.39%)543774.0 WDrop High
4 mm²32 A25 A356.76 V (89.19%)43.2 V588.49 V (147.12%)339858.8 WDrop High
6 mm²41 A32 A237.84 V (59.46%)162.2 V392.32 V (98.08%)226572.5 WDrop High
10 mm²57 A44 A142.7 V (35.68%)257.3 V235.39 V (58.85%)135943.5 WDrop High
16 mm²76 A59 A89.19 V (22.3%)310.8 V147.12 V (36.78%)84964.7 WDrop High
25 mm²101 A78 A57.08 V (14.27%)342.9 V94.16 V (23.54%)54377.4 WDrop High
35 mm²125 A97 A40.77 V (10.19%)359.2 V67.26 V (16.81%)38841.0 WDrop High
50 mm²151 A118 A28.54 V (7.14%)371.5 V47.08 V (11.77%)27188.7 WDrop High
70 mm²192 A150 A20.39 V (5.1%)379.6 V33.63 V (8.41%)19420.5 WDrop High
95 mm²232 A181 A15.02 V (3.76%)385.0 V24.78 V (6.19%)14309.8 WDrop High
120 mm²269 A210 A11.89 V (2.97%)388.1 V19.62 V (4.9%)11328.6 WDrop High
150 mm²309 A241 A9.51 V (2.38%)390.5 V15.69 V (3.92%)9062.9 WDrop High
185 mm²353 A275 A7.71 V (1.93%)392.3 V12.72 V (3.18%)7348.3 WDrop High
240 mm²415 A324 A5.95 V (1.49%)394.1 V9.81 V (2.45%)5664.3 WDrop High
300 mm²477 A372 A4.76 V (1.19%)395.2 V7.85 V (1.96%)4531.4 WDrop High
400 mm²570 A445 A3.57 V (0.89%)396.4 V5.88 V (1.47%)3398.6 W✓ OK (≤3%)

FAQ — Kabelarea för 550 Ampere vid 70 Meter (400V)

Vilken kabelarea krävs för 550A vid 70 meter (400V)?

För 550 Ampere över 70 meter vid 400V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (3.57V / 0.89%).

Hur stor effekt motsvarar 550A vid 400V?

Det motsvarar 381.05 kW med en rekommenderad säkring på 600A.