⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 550 Ampere vid 35 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 550 A över 35 m vid 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 1.78V (0.45%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.94V (0.74%)
Voltage at Load398.2 VLine Loss: 1699.3 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A475.68 V (118.92%)0.0 V784.65 V (196.16%)453145.0 WDrop High
2.5 mm²24 A18 A285.41 V (71.35%)114.6 V470.79 V (117.7%)271887.0 WDrop High
4 mm²32 A25 A178.38 V (44.59%)221.6 V294.24 V (73.56%)169929.4 WDrop High
6 mm²41 A32 A118.92 V (29.73%)281.1 V196.16 V (49.04%)113286.2 WDrop High
10 mm²57 A44 A71.35 V (17.84%)328.6 V117.7 V (29.42%)67971.8 WDrop High
16 mm²76 A59 A44.59 V (11.15%)355.4 V73.56 V (18.39%)42482.3 WDrop High
25 mm²101 A78 A28.54 V (7.14%)371.5 V47.08 V (11.77%)27188.7 WDrop High
35 mm²125 A97 A20.39 V (5.1%)379.6 V33.63 V (8.41%)19420.5 WDrop High
50 mm²151 A118 A14.27 V (3.57%)385.7 V23.54 V (5.88%)13594.4 WDrop High
70 mm²192 A150 A10.19 V (2.55%)389.8 V16.81 V (4.2%)9710.2 WDrop High
95 mm²232 A181 A7.51 V (1.88%)392.5 V12.39 V (3.1%)7154.9 WDrop High
120 mm²269 A210 A5.95 V (1.49%)394.1 V9.81 V (2.45%)5664.3 WDrop High
150 mm²309 A241 A4.76 V (1.19%)395.2 V7.85 V (1.96%)4531.4 WDrop High
185 mm²353 A275 A3.86 V (0.96%)396.1 V6.36 V (1.59%)3674.1 WDrop High
240 mm²415 A324 A2.97 V (0.74%)397.0 V4.9 V (1.23%)2832.2 WDrop High
300 mm²477 A372 A2.38 V (0.59%)397.6 V3.92 V (0.98%)2265.7 WDrop High
400 mm²570 A445 A1.78 V (0.45%)398.2 V2.94 V (0.74%)1699.3 W✓ OK (≤3%)

FAQ — Kabelarea för 550 Ampere vid 35 Meter (400V)

Vilken kabelarea krävs för 550A vid 35 meter (400V)?

För 550 Ampere över 35 meter vid 400V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (1.78V / 0.45%).

Hur stor effekt motsvarar 550A vid 400V?

Det motsvarar 381.05 kW med en rekommenderad säkring på 600A.