Kabelarea för 550 Ampere vid 30 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 550 A över 30 m vid 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 1.53V (0.38%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.52V (0.63%)
Voltage at Load398.5 VLine Loss: 1456.5 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A407.72 V (101.93%)0.0 V672.56 V (168.14%)388410.0 WDrop High
2.5 mm²24 A18 A244.63 V (61.16%)155.4 V403.53 V (100.88%)233046.0 WDrop High
4 mm²32 A25 A152.9 V (38.22%)247.1 V252.21 V (63.05%)145653.8 WDrop High
6 mm²41 A32 A101.93 V (25.48%)298.1 V168.14 V (42.03%)97102.5 WDrop High
10 mm²57 A44 A61.16 V (15.29%)338.8 V100.88 V (25.22%)58261.5 WDrop High
16 mm²76 A59 A38.22 V (9.56%)361.8 V63.05 V (15.76%)36413.4 WDrop High
25 mm²101 A78 A24.46 V (6.12%)375.5 V40.35 V (10.09%)23304.6 WDrop High
35 mm²125 A97 A17.47 V (4.37%)382.5 V28.82 V (7.21%)16646.1 WDrop High
50 mm²151 A118 A12.23 V (3.06%)387.8 V20.18 V (5.04%)11652.3 WDrop High
70 mm²192 A150 A8.74 V (2.18%)391.3 V14.41 V (3.6%)8323.1 WDrop High
95 mm²232 A181 A6.44 V (1.61%)393.6 V10.62 V (2.65%)6132.8 WDrop High
120 mm²269 A210 A5.1 V (1.27%)394.9 V8.41 V (2.1%)4855.1 WDrop High
150 mm²309 A241 A4.08 V (1.02%)395.9 V6.73 V (1.68%)3884.1 WDrop High
185 mm²353 A275 A3.31 V (0.83%)396.7 V5.45 V (1.36%)3149.3 WDrop High
240 mm²415 A324 A2.55 V (0.64%)397.5 V4.2 V (1.05%)2427.6 WDrop High
300 mm²477 A372 A2.04 V (0.51%)398.0 V3.36 V (0.84%)1942.0 WDrop High
400 mm²570 A445 A1.53 V (0.38%)398.5 V2.52 V (0.63%)1456.5 W✓ OK (≤3%)

FAQ — Kabelarea för 550 Ampere vid 30 Meter (400V)

Vilken kabelarea krävs för 550A vid 30 meter (400V)?

För 550 Ampere över 30 meter vid 400V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (1.53V / 0.38%).

Hur stor effekt motsvarar 550A vid 400V?

Det motsvarar 381.05 kW med en rekommenderad säkring på 600A.