Kabelarea för 60 Ampere vid 400 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 60 A över 400 m vid 400V.

Copper Cable (≤3% Drop)95 mm²Drop: 9.36V (2.34%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 9.78V (2.45%)
Voltage at Load390.6 VLine Loss: 973.1 W
Max Power & Breaker41.57 kW60A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A593.05 V (148.26%)0.0 V978.26 V (244.57%)61632.0 WDrop High
2.5 mm²24 A18 A355.83 V (88.96%)44.2 V586.96 V (146.74%)36979.2 WDrop High
4 mm²32 A25 A222.4 V (55.6%)177.6 V366.85 V (91.71%)23112.0 WDrop High
6 mm²41 A32 A148.26 V (37.07%)251.7 V244.57 V (61.14%)15408.0 WDrop High
10 mm²57 A44 A88.96 V (22.24%)311.0 V146.74 V (36.68%)9244.8 WDrop High
16 mm²76 A59 A55.6 V (13.9%)344.4 V91.71 V (22.93%)5778.0 WDrop High
25 mm²101 A78 A35.58 V (8.9%)364.4 V58.7 V (14.67%)3697.9 WDrop High
35 mm²125 A97 A25.42 V (6.35%)374.6 V41.93 V (10.48%)2641.4 WDrop High
50 mm²151 A118 A17.79 V (4.45%)382.2 V29.35 V (7.34%)1849.0 W~ ≤5%
70 mm²192 A150 A12.71 V (3.18%)387.3 V20.96 V (5.24%)1320.7 W~ ≤5%
95 mm²232 A181 A9.36 V (2.34%)390.6 V15.45 V (3.86%)973.1 W✓ OK (≤3%)
120 mm²269 A210 A7.41 V (1.85%)392.6 V12.23 V (3.06%)770.4 W✓ OK (≤3%)
150 mm²309 A241 A5.93 V (1.48%)394.1 V9.78 V (2.45%)616.3 W✓ OK (≤3%)
185 mm²353 A275 A4.81 V (1.2%)395.2 V7.93 V (1.98%)499.7 W✓ OK (≤3%)
240 mm²415 A324 A3.71 V (0.93%)396.3 V6.11 V (1.53%)385.2 W✓ OK (≤3%)
300 mm²477 A372 A2.97 V (0.74%)397.0 V4.89 V (1.22%)308.2 W✓ OK (≤3%)
400 mm²570 A445 A2.22 V (0.56%)397.8 V3.67 V (0.92%)231.1 W✓ OK (≤3%)

FAQ — Kabelarea för 60 Ampere vid 400 Meter (400V)

Vilken kabelarea krävs för 60A vid 400 meter (400V)?

För 60 Ampere över 400 meter vid 400V rekommenderas 95 mm² kopparkabel för att hålla spänningsfallet under 3% (9.36V / 2.34%).

Hur stor effekt motsvarar 60A vid 400V?

Det motsvarar 41.57 kW med en rekommenderad säkring på 60A.