Kabelarea för 600 Ampere vid 300 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 600 A över 300 m vid 400V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 8.34V (2.08%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 27.51V (6.88%)
Voltage at Load391.7 VLine Loss: 8667.0 W
Max Power & Breaker415.69 kW600A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 300m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 4447.91 V (1111.98%) | 0.0 V | 7336.97 V (1834.24%) | 4622400.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 2668.74 V (667.19%) | 0.0 V | 4402.18 V (1100.55%) | 2773440.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 1667.96 V (416.99%) | 0.0 V | 2751.36 V (687.84%) | 1733400.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 1111.98 V (277.99%) | 0.0 V | 1834.24 V (458.56%) | 1155600.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 667.19 V (166.8%) | 0.0 V | 1100.55 V (275.14%) | 693360.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 416.99 V (104.25%) | 0.0 V | 687.84 V (171.96%) | 433350.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 266.87 V (66.72%) | 133.1 V | 440.22 V (110.05%) | 277344.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 190.62 V (47.66%) | 209.4 V | 314.44 V (78.61%) | 198102.9 W | Drop High |
| 50 mm² | 151 A | 118 A | 133.44 V (33.36%) | 266.6 V | 220.11 V (55.03%) | 138672.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 95.31 V (23.83%) | 304.7 V | 157.22 V (39.31%) | 99051.4 W | Drop High |
| 95 mm² | 232 A | 181 A | 70.23 V (17.56%) | 329.8 V | 115.85 V (28.96%) | 72985.3 W | Drop High |
| 120 mm² | 269 A | 210 A | 55.6 V (13.9%) | 344.4 V | 91.71 V (22.93%) | 57780.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 44.48 V (11.12%) | 355.5 V | 73.37 V (18.34%) | 46224.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 36.06 V (9.02%) | 363.9 V | 59.49 V (14.87%) | 37478.9 W | Drop High |
| 240 mm² | 415 A | 324 A | 27.8 V (6.95%) | 372.2 V | 45.86 V (11.46%) | 28890.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 22.24 V (5.56%) | 377.8 V | 36.68 V (9.17%) | 23112.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 16.68 V (4.17%) | 383.3 V | 27.51 V (6.88%) | 17334.0 W | Drop High |
FAQ — Kabelarea för 600 Ampere vid 300 Meter (400V)
Vilken kabelarea krävs för 600A vid 300 meter (400V)?
För 600 Ampere över 300 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (8.34V / 2.08%).
Hur stor effekt motsvarar 600A vid 400V?
Det motsvarar 415.69 kW med en rekommenderad säkring på 600A.
Related Lengths & Currents (400V)
600A · 5m (400V)600A · 10m (400V)600A · 15m (400V)600A · 20m (400V)600A · 25m (400V)600A · 30m (400V)600A · 35m (400V)600A · 40m (400V)600A · 45m (400V)600A · 50m (400V)600A · 60m (400V)600A · 70m (400V)10A · 300m (400V)16A · 300m (400V)20A · 300m (400V)25A · 300m (400V)32A · 300m (400V)40A · 300m (400V)50A · 300m (400V)63A · 300m (400V)80A · 300m (400V)100A · 300m (400V)125A · 300m (400V)160A · 300m (400V)200A · 300m (400V)