Kabelarea för 63 Ampere vid 300 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 300 m vid 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 10.01V (2.5%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 9.63V (2.41%)
Voltage at Load390.0 VLine Loss: 1092.0 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A467.03 V (116.76%)0.0 V770.38 V (192.6%)50962.0 WDrop High
2.5 mm²24 A18 A280.22 V (70.05%)119.8 V462.23 V (115.56%)30577.2 WDrop High
4 mm²32 A25 A175.14 V (43.78%)224.9 V288.89 V (72.22%)19110.7 WDrop High
6 mm²41 A32 A116.76 V (29.19%)283.2 V192.6 V (48.15%)12740.5 WDrop High
10 mm²57 A44 A70.05 V (17.51%)329.9 V115.56 V (28.89%)7644.3 WDrop High
16 mm²76 A59 A43.78 V (10.95%)356.2 V72.22 V (18.06%)4777.7 WDrop High
25 mm²101 A78 A28.02 V (7.01%)372.0 V46.22 V (11.56%)3057.7 WDrop High
35 mm²125 A97 A20.02 V (5.0%)380.0 V33.02 V (8.25%)2184.1 WDrop High
50 mm²151 A118 A14.01 V (3.5%)386.0 V23.11 V (5.78%)1528.9 W~ ≤5%
70 mm²192 A150 A10.01 V (2.5%)390.0 V16.51 V (4.13%)1092.0 W✓ OK (≤3%)
95 mm²232 A181 A7.37 V (1.84%)392.6 V12.16 V (3.04%)804.7 W✓ OK (≤3%)
120 mm²269 A210 A5.84 V (1.46%)394.2 V9.63 V (2.41%)637.0 W✓ OK (≤3%)
150 mm²309 A241 A4.67 V (1.17%)395.3 V7.7 V (1.93%)509.6 W✓ OK (≤3%)
185 mm²353 A275 A3.79 V (0.95%)396.2 V6.25 V (1.56%)413.2 W✓ OK (≤3%)
240 mm²415 A324 A2.92 V (0.73%)397.1 V4.81 V (1.2%)318.5 W✓ OK (≤3%)
300 mm²477 A372 A2.34 V (0.58%)397.7 V3.85 V (0.96%)254.8 W✓ OK (≤3%)
400 mm²570 A445 A1.75 V (0.44%)398.2 V2.89 V (0.72%)191.1 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 300 Meter (400V)

Vilken kabelarea krävs för 63A vid 300 meter (400V)?

För 63 Ampere över 300 meter vid 400V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (10.01V / 2.5%).

Hur stor effekt motsvarar 63A vid 400V?

Det motsvarar 43.65 kW med en rekommenderad säkring på 63A.